Operating Modes
Offi ce Pro 36 operates in 2 modes, FAN Only and COOL. When in FAN Only mode, the unit 
circulates the surrounding air. When in COOL mode, the compressor is operational and 
cool air is circulated.
• 
COOL Mode
 
Offi ce Pro 36 will operate in FAN Only mode for approximately 120 seconds before 
the compressor engages. (Time delay setting is 120 ±15 seconds.) 
• 
Temperature Control
 
The room temperature thermistor allows the unit to switch automatically between 
COOL and FAN Only modes. This is dependent upon inlet air temperature versus SET 
POINT temperature.
• 
Fan Mode Control DIP Switch
 
The Fan Mode Control DIP Switch determines whether the FAN will continue to oper-
ate or stop when the compressor cycles off. (SET POINT temperature equals inlet 
air or room temperature.) The unit has been preset at the factory for continuous fan 
operation.
• 
Temperature Scale Display DIP Switch
 
The Temperature Scale Display DIP Switch changes the temperature(s) that are 
displayed to either °C or °F. The unit has been preset from the factory to display the 
temperature(s) in °F. 
NOTE: If you wish to change the fan mode operation (COOL[OPERATE to 
COOL
[STOP), and/or the Temperature Scale Display (°F to °C), contact your Movin-
Cool reseller.
Emptying the Drain Tank (If equipped)
During COOL mode, condensate will accumulate in the drain tank. When the drain tank 
becomes full, the FULL TANK LED will fl ash and the unit will shut off automatically.
NOTE: If you want to empty the drain tank, while the unit is in operation, press the 
COOL ON/OFF button to turn the unit off. If a pro-
gram is running, you must fi rst press the Program 
RUN button.
 
Open the front panel.
 
Pull the drain tank from the unit.
 
Remove the cap and empty the drain tank.
 
Replace the cap and return the drain tank to the 
unit.
 
Close the drain tank lid.
 
If the Program RUN LED is fl ashing, press the 
COOL ON/OFF button to continue running the 
program. If the Program RUN LED is illuminated 
continuously, no further steps are necessary.  If 
no program exists or the program was deacti-
vated, press the COOL ON/OFF button to restart 
the unit.