Справочник Пользователя для American Water Heater VGD625T 100

Скачать
Страница из 60
19
MIXING VALVES
Water temperature over 125°F (52°C)
can cause severe burns instantly
resulting in severe injury or death.
Children, the elderly and the
physically or mentally disabled are at
highest risk for scald injury.
Feel water before bathing or
showering.
Temperature limiting devices such as
mixing valves must be installed
when required by codes and to
ensure safe temperatures at fixtures.
Water heated to a temperature which will satisfy clothes washing, 
dish  washing,  and  other  sanitizing  needs  can  scald  and  cause 
permanent  injury  upon  contact.  Short  repeated  heating  cycles 
caused  by  small  hot  water  uses  can  cause  temperatures  at  the 
point of use to exceed the water heater’s temperature setting by 
up to 20°F (11°C).
Some people are more likely to be permanently injured by hot water 
than others. These include the elderly, children, the infirm and the 
physically/mentally disabled. Table 4 shows the approximate time-
to-burn relationship for normal adult skin. If anyone using hot water 
provided by the water heater being installed fits into one of these 
groups or if there is a local code or state law requiring a certain 
water  temperature  at  the  point  of  use,  then  special  precautions 
must be taken.
In  addition  to  using  the  lowest  possible  temperature  setting  that 
satisfies the demand of the application a Mixing Valve should be 
installed  at  the  water  heater  or  at  the  hot  water  taps  to  further 
reduce system water temperature.
Mixing  valves  are  available  at  plumbing  supply  stores.  Consult 
a  Qualified  Installer  or  Service  Agency.  Follow  mixing  valve 
manufacturer’s instructions for installation of the valves.
In all cases, the following burn table must be used.
Table 4
Water Temperature
 °F (°C)
Time for 1st Degree Burn
(Less Severe Burns)
Time for Permanent 
Burns
2nd & 3rd Degree
(Most Severe Burns)
110 (43.3)
(normal shower temp.)
116 (46.7)
(pain threshold)
116 (46.7)
35 minutes
45 minutes
122 (50)
1 minute
5 minutes
131 (55)
5 seconds
25 seconds
140 (60)
2 seconds
5 seconds
149 (65)
1 second
2 seconds
154 (67.8)
instantaneous
1 second
(U.S. Government Memorandum, C.P.S.C., Peter L. Armstrong, Sept. 15, 1978)
GAS PIPING
Make sure gas supplied is same type listed on model rating plate. The 
inlet gas pressure must not exceed 14 inch water column (3.5 kPa) for 
natural and propane gas (L.P.). The minimum inlet gas pressure shown 
on rating plate is that which will permit firing at rated input.
SEDIMENT TRAPS
A  sediment  trap  shall  be  installed  as  close  to  the  gas  inlet  of  the 
water heater as practical at the time of water heater installation. The 
sediment trap shall be either a tee fitting with a capped nipple in the 
bottom  outlet  or  other  device  recognized  as  an  effective  sediment 
trap.
Contaminants in the gas lines may cause improper operation of the 
gas control valve that may result in fire or explosion. Before attaching 
the gas line be sure that all gas pipe is clean on the inside. To trap 
any dirt or foreign material in the gas supply line, a sediment trap 
must be incorporated in the piping. The sediment trap must be readily 
accessible. Install in accordance with the Gas Piping section. Refer 
to the current edition of the National Fuel Gas Code (ANSI Z223.1/
NFPA 54).
Use pipe joint compound or teflon tape marked as being resistant to 
the action of petroleum [Propane (L.P.)] gases. 
The water heater and its gas connection must be leak tested before 
placing the water heater in operation.
The water heater and its individual Shut-off valve shall be disconnected 
from the gas supply piping system during any pressure testing of that 
system at test pressures in excess of 1/2 pound per square inch (3.5 
kPa). It shall be isolated from the gas supply piping system by closing 
its individual manual Shut-off valve during any pressure testing of the 
gas supply piping system at test pressures equal to or less than 1/2 
pound per square inch (3.5 kPa).