CONCENTRIC VENT INSTALLATION
This water heater is certified for concentric venting with concentric 
vent  kit  #9006328005.  Follow  instructions  below  for  proper 
installations.
Table 8 – KIT COMPONENTS
Field  supplied  pipe  and  fittings  are  required  to  complete  the 
installation.
This concentric vent termination kit may be used with 3 inch diameter 
pipe systems.
SAFETY CONSIDERATIONS
Installing and servicing water heating equipment can be hazardous 
due  to  gas  and  electrical  components.  Installation  and  service  of 
the concentric vent termination requires ability equivalent to that of 
a qualified installer or qualified service technician, see Page 7. All 
precautions in the literature, on tags, and labels attached to the unit 
must be observed. 
Follow all safety codes. Wear safety glasses and work gloves.
Figure: 24
Figure: 25
*    Dimension  21  1/8  in.  may  be  lengthened  to  60  in.  maximum.  
    Dimension  21  1/8  in.  may  also  be  shortened  by  cutting  the  
    pipes, provided in the kit, to 12 in. minimum.
**   Dimension  39  will  change  accordingly  as  dimension  
    21 1/8 in. is lengthened or shortened.
Do not use field-supplied couplings to extend pipes. Airflow restriction 
will  occur  and  the  heater  pressure  switch  may  cause  intermittent 
operation.
INSTALLATION VERTICAL ROOF TERMINATION 
1.  Determine best location for termination kit.
NOTE:  Roof  termination  is  preferred  since  it  is  less 
susceptible to damage, has reduced chances to intake contaminants, 
and less visible vent vapors.
2.  Cut 1 hole (5 in. diameter)
3.  Partially assemble concentric vent termination kit. 
  a)  Cement  Y  concentric  fitting  to  larger  diameter  kit  
pipe, see Figure 24.
  b)  Cement rain cap to smaller diameter kit pipe, see Figure 26.
Figure: 26
NOTE: Instead of cementing the smaller pipe to the rain cap, a 
field-supplied stainless steel screw may be used to secure the 
2  components  together  when  field  disassembly  is  desired  for 
cleaning, see Figure 26.
When using alternate screw method, drill clearance hole in rain 
cap and pilot hole in vent pipe for screw size being used. Failure 
to drill adequate holes may cause cracking of PVC components, 
allowing combustion products to be recirculated. Failure to follow 
this warning could result in personal injury or death.
Do not operate the heater with rain cap removed or recirculation 
of combustion products may occur. Water may also collect inside 
larger  combustion-air  pipe  and  flow  to  the  burner  enclosure. 
Failure to follow this warning could result in product damage or 
improper operation, personal injury or death.
4.  Install  Y  concentric  fitting  and  pipe  assembly  through 
structure’s hole and field supplied roof boot/flashing.
Figure: 27