Справочник Пользователя для American Water Heater Commercial Ultra Low NOx Gas water Heater

Скачать
Страница из 24
2
FOREWORD
The design of model BBCN375T754NV complies with the current edition 
of ANSI Z21.10.3/CSA 4.3 as automatic storage or automatic circulating 
tank type water heaters.
Installation diagrams are found in this manual.  These diagrams will serve 
to provide the installer with a reference for the materials and method of 
piping necessary.  It is highly essential that all water and gas piping be 
installed as shown on the diagrams.
In addition to these instructions, the equipment shall be installed in 
accordance with those installation regulations in force in the local area 
where the installation is to be made.  These shall be carefully followed 
in all cases.  Authorities having jurisdiction should be consulted before 
installations are made.
ROUGH-IN DIMENSIONS
FIGURE 1.
The installation must conform to these instructions and the local code 
authority having jurisdiction.  
In the absence of local codes, the installation must comply with the following:
In the United States:
Current edition of the National Fuel Gas Code, ANSI Z223.1 / NFPA 54 
and the National Electrical Code, NFPA 70;
In Canada:
Current edition of the Installation Code CAN/CSA-B149.1 and the 
Canadian Electrical Code CSA C22.1.
These are available from Canadian Standards Association, 8501 East 
Pleasant Valley Road, Cleveland, OH 44131 or National Fire Protection 
Association, 1 Batterymarch Park, Quincy, MA 02269.
*INSTALL IN ACCORDANCE WITH LOCAL CODES
TOP VIEW
TABLE 3, GAS AND ELECTRICAL CHARACTERISTICS
All Models:  Maximum supply pressure = 14.0 in. W.C. (3.48 kPa)
 
Minimum supply pressure, Natural gas = 6 in. W.C. (1.49 kPa). 
 
Minimum pressures must be maintained under both load and no load (static and dynamic) conditions.
Recovery ratings are based on 80% thermal efficiency. 
TABLE 1, DIMENSIONS
Units
A
B
C
D
E
F
G
H
J
K
L
M
Inches
CM
66 5/8
169.22
58 3/4
134.23
30 15/16
78.58
27 3/4
70.5
15 1/4
38.6
4
10.2
15 3/4
40.0
16
40.6
1 1/4
3.2
1 1/4
NPT
1/2
NPT
12 1/4
31.1
TABLE 2, RECOVERY RATINGS
Manifold Pressure
Electrical Characteristics
Type of gas
Inches W.C.
kPa
Voltz/Hz
Amperes
Natural Gas
4.0
1.12
120/160
<5
INPUT RATE
Recovery in US Gallons/hr or Liters/hr at Indicated Temperature Rise in Fahrenheit or Celsius
75,100    BTU/H
°F
30
40
50
60
70
80
90
100
110
120
130
140
GPH
243
182
145
122
104
91
81
73
66
60
56
52
22           KW
°C
17
23
28
33
39
44
50
56
61
67
72
78
LPH
920
688
549
460
392
344
306
277
251
228
213
199