DEFINITY Enterprise Communications Server Release 7 
Maintenance for R7r  
555-230-126  
Issue 4
June 1999
Maintenance Commands 
8-42
busyout journal-printer 
8
Parameters
Examples
For more information see the following sections at the beginning of this chapter: 
Busyout and Release Commands, Common Input Parameters, and Common 
Output Fields.
busyout journal-printer
busyout journal-printer pms-log | wakeup-log
The busyout journal-printer command puts the link to the Property 
Management System log or wakeup log printers in a maintenance busy state. 
(See Busyout and Release Commands at the beginning of this chapter). When 
busied out, the link is dropped and no data transfer can take place over it.
This command can be used to prevent unwanted interference between different 
maintenance processes. Maintenance software may put a component that is part 
of a link in a busy state, causing link set-up to fail, and resulting in attempts by 
the system to reestablish the link. If a maintenance test requires that the 
component be idle, frequent attempts at re-setup may delay the recovery of a 
faulty component. Busying out the link will prevent re-setup attempts.
Parameters
Examples
busyout journal-printer pms-log
busyout journal-printer wakeup-log
For more information see the following sections at the beginning of this chapter: 
Busyout and Release Commands, Common Input Parameters, and Common 
Output Fields.
C
The cabinet is always 1 and need not be entered. On systems with duplicated 
SPEs only, carrier a or b must be entered.
Simplex:
busyout host-adapter
Duplicated:
busyout host-adapter b
pms-log
Busies out the link to the Property Management System printer
wakeup-log
Busies out the link to the Wakeup Log printer