DEFINITY Enterprise Communications Server Release 6
Installation and Test for Multi-Carrier Cabinets  
555-230-112  
Issue 5
May 1998
Install and Wire Telephones and Other Equipment 
Page 5-46
1145B Power Supply 
5
Wall-Mounting Plates
The top plate is used for mounting the back-up battery. The bottom plate is used 
to mount the power supply and distribution units. The plates can be rack- 
mounted using standard rack-mounting brackets.
1. Locate 1 plate directly below the other such that the AC power cord (6.5 
feet or 2 meters) reaches the electrical outlet from a power supply 
mounted on the bottom plate. Both plates should be located so the raised 
letters are right side up.
NOTE:
A maximum of 4 power supplies can be powered from 1 dedicated 
110 VAC, 20 amp (or 230 VAC, 15 amp) feeder. Use only unswitched 
receptacles (receptacles not connected to a wall switch).
2. Secure the wall mounting plates to a standard 3/4 inch (2 cm) thick 
plywood mounting board. Each mounting plate comes with four #10 x 
1/2-inch wood screws.
3. The 1145B Power Supply is snap-fit onto the bottom wall mounting plate 
without tools.
4. An installer-provided insulated ground wire, 16 AWG (1.5 mm
2
) or greater, 
is required to connect the power supply frame ground lug to an approved 
ground. The frame ground screw is located next to the AC receptacle, to 
the left of the unit.
5. Mark the Unit Number and Connectivity information on the front label next 
to the LEDs.