DEFINITY Enterprise Communications Server Release 6
Installation and Test for Multi-Carrier Cabinets  
555-230-112  
Issue 5
May 1998
Cable Ductwork 
Page C-9
 
C
8. Route the appropriate cables between the cabinets just connected.
9. If a given cabinet is to support a cross-aisle shielded duct, set a 
cross-aisle riser (“C” in 
on the cabinet riser (“A”). Otherwise 
set a shielded coupling (“D”) on the cabinet riser. In either case, position 
the device so the two holes on the back wall line up with the holes on the 
back wall of the cabinet riser. Bolt the two pieces together at the holes just 
described.
10. If there is no trough to install in one end of the cabinet riser, press a 
shielded end cap (“E”) on the unused end of the riser. The side walls of 
the end cap go inside the walls of the riser and outside of the ears of the 
riser. The top of the end cap should rest on top of the shielded coupling or 
cross-aisle riser previously installed. Bolt the bottom of the end cap to the 
cabinet riser with a self-tapping screw.
11. Set the shielded cover (“D”) on the shielded trough (“B”) and press it 
down so the dimples on the cover engage the holes in the trough.
Install Cross-Aisle Shielded Ducts
The inter-cabinet ducts and cross-aisle risers must be installed before any 
cross-aisle ductwork is installed.
1. Set the tongue on the bottom of a cross-aisle trough (“G” in 
into the platform of the cross-aisle riser (“C”). From above the trough, run a 
self-tapping screw through the slot in the trough and into the hole in the 
riser.