Issue 5
May 1998
Install and Connect Cabinets 
Page 1-25
Connect Remote Power Off Cable and External Alarm Cable 
1
Connect Remote Power Off Cable and 
External Alarm Cable
Figure 1-9
 shows the location of the Remote Power Off (RPO) cable. The 
opposite end of the cable connects to the Emergency Power Off (EPO) switch 
located outside of the equipment room.
Figure 1-9.
Remote Power Off Cable Connections 
 
Part 1
Even though the equipment room EPO switch disconnects main AC power to the 
equipment room, it cannot disconnect the battery power from the J58890CH. An 
auxiliary set of contacts inside the EPO are used for this function. 
1. Plug the RPO cable into the connector shown in 
Figure 1-9
.
2. Route the opposite end of the wires to the EPO switch. The opposite end 
of the RPO cable connects to the internal relay.
NOTE:
The EPO switch and the auxiliary contacts (inside the EPO switch 
assembly) are customer-provided.
Connect RPO
cable here (J21)
Connect external
alarm cable here
(J18)
Carrier
circuit
breakers
psdf002 CJL 081596
External
alarm cable
Pin 6 (-RPO)
Pin 2 (+RPO)