Справочник Пользователя для Lucent Technologies Release 6

Скачать
Страница из 453
DEFINITY Enterprise Communications Server Release 6
Installation and Test for Multi-Carrier Cabinets  
555-230-112  
Issue 5
May 1998
Install Telecommunications Cabling 
Page 2-33
Station Circuit Distribution from Equipment Room 
2
Satellite Locations
Satellite locations are closets that provide an administration point (using 
cross-connect equipment) for station cables and where adjunct power may be 
applied. The station cable circuits from the equipment room MDF are 3-pair. At 
the satellite location, 4-pair circuits run to the information outlets. The hardware 
used is 110-type terminal blocks.
Satellite Locations Using 110-Type Hardware
Each terminal block has a 3-pair (white field) and a 4-pair (blue field) located on 
the same terminal block. 
The 110A-type terminal block that can be used is the 110AE1-75FT. It must be 
field-terminated to both the white and blue fields.
The 300-pair 110P-type terminal blocks that can be used are:
110PE1-300CT/FT 
 25-pair connector on the white field and 
field-terminated on the blue field
110PE1-300FT 
 Field-terminated on both the white and blue fields
The 900-pair 110P-type terminal blocks that can be used are:
110PE1-900CT/FT 
 25-pair connector on the white field and 
field-terminated on the blue field
110PE1-900FT 
 Field-terminated on both the white and blue fields
Station Circuit Distribution from 
Equipment Room
This section explains the station circuit distribution from the equipment room to 
the information outlets for new wiring installations. Example connection diagrams 
are provided to show the options for running and connecting the station cables.
If most of the telephones/voice terminals that require remote powering are within 
250 feet (76.2 m) of the equipment room, 4-pair station circuits are run from the 
equipment room to the information outlets. If this is not the case, or if the 
customer requires 2-point administration, 3-pair station circuits are run from the 
equipment room to satellite locations. Then, the 4-pair station circuits are run 
from the satellite locations to the information outlets.
A list of voice and data terminals that can be connected to the system is 
provided in 
Table 2-4 on page 2-40
. A list of administration terminals that can be 
connected to the system is provided in 
Table 2-5 on page 2-44
.