MATE - AC INPUT CONTROL 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
AC Input Control 
The OutBack MATE includes a AC IN “hot” key to allow direct control of the AC input from anywhere in the menu system. The AC IN 
key is located on the left side of the MATE’s LCD display. Above the AC IN key is a yellow LED indicator which flashes when an AC 
source is available but not connected, and is on continuously when the AC source is connected.  If no AC source is available, the 
yellow LED indicator will remain off.  The screens shown on this page apply to the “MATE”, the “MATE B”, and the “MATE 2” only. 
 
 
 
 
AC INPUT CONTROL 
currently:       USE 
 
DROP  USE         OK 
 
 
 
 
GEN START CONTROL 
currently:    MAN-OFF 
 
OFF  AUTO  ON     OK 
 
 
 
 
CHARGER CONTROL 
currently:       AUTO 
 
OFF   AUTO        OK 
 
 
 
 
CHARGER MODE CONTROL 
global charger mode 
 
BULK   EQ          OK 
 
BULK CONTROL 
 
 
START  STOP        OK 
 
 
Pressing the AC IN key once brings up the AC INPUT CONTROL screen.  USE enables the 
inverter to connect to the AC source when it is available.  DROP disconnects the AC source 
but will allow it to be reconnected if the battery gets too low or the inverter is overloaded.   
 
 
 
Pressing the AC IN key a second time brings up the GEN START CONTROL screen. This 
allows operation of the generator either manually or automatically using the Advanced 
Generator Start (AGS) functions.  The generators starting circuitry must be connected to the 
AUX ports of the control terminal block (see pages 12 & 13) to use this screen to manually turn 
the generator ON or OFF or to let the FX automatically perform the AGS functions.  When the 
AGS functions have not been programmed, the screen will show MAN-OFF indicating that the 
generator is controlled manually and is OFF.  Pressing the <ON> button will change the 
screen into MAN-ON and the generator will turn ON.  To put this screen in AUTO mode, you 
must access the AGS SETUP menu.  See your MATE manual for details. 
 
Pressing the AC IN key a third time brings up the CHARGER CONTROL screen. This allows 
operation of the battery charger to be preset for when an AC source is available.  In AUTO 
mode the charger will start charging when an AC source connects to the FX or when the FX 
decides the batteries need charging.  In OFF mode the charger stays off but the AC source is 
still passed through to the loads.  
 
 
 
Pressing the AC IN key a fourth time brings up the CHARGER MODE CONTROL screen. This 
screen allows the MATE to issue system wide (global) charger commands. Both OutBack MX 
and FX products will respond to global charger commands if they are connected together 
through the HUB. 
 
Pressing <BULK> brings up the BULK CONTROL screen, it will allow the user to start and/or 
stop a bulk charge cycle manually by pressing <START> or <STOP> respectively. 
 
Pressing <EQ> brings up the EQUALIZE CONTROL screen.   
 
When <START> has been selected, two informational screens are displayed.  The user then 
must answer <YES> before an equalize charging cycle is allowed to begin.  
 
Once the equalizing process has started, you can stop it at anytime by selecting <STOP> from 
this same control screen. 