7.  Diagnosis 
7.4  PLC Interface Diagnosis 
 
 
 
I-287 
7.4.3  PLC Interface Signal Forcible Definition (Single-shot Type) 
 
 
This function is used to forcibly define signals to check the PLC functions. 
 
This function is available for the following device numbers: X, Y, U, W, S, M, G, F, L, E, T, Q, C, B, D, and R. 
 (1) 
Mode 
setting 
 
 
Set the device number to be forcibly set in DEVICE (   ), definition data in DATA (   ), and 1 in MODE 
(   ), then press the 
 
 
INPUT 
 key. The setup data is processed and forcibly defined at the top of one cycle of 
user PLC. 
 
Press the 
 
 
INPUT 
 key. 
Set M23 in DEVICE (      ), 
1 in DATA (      ), and 
1 in MODE (      ). 
ALARM SERVO SPINDLE 
PLC-I/F 
MENU 
 [PLC-I/F] 
ALARM/DIAGN 4 
 <SET 
DATA> 
 
 
 
 76543210 
HEX   
76543210 
HEX
  M0000 oooooooo 
00 
D0005  oooooooo 
00
  M0008 ooooo1o1 
05 
  o11oo1oo 
64
  M0016 oooooooo 
00 
D0006  1oooooo1 
81
  M0024 o1o1oooo 
50 
  ooooo1oo 
04
     
     
     
     
  DEVICE  DATA 
MODE  DEVICE  DATA  MODE
  ( M23  )  (   1 )   ( 1) 
(      )  (     )   (  ) 
 [PLC-I/F] 
ALARM/DIAGN 4 
 <SET 
DATA> 
 
 
 
 76543210 
HEX   
76543210 
HEX
  M0016 oooooooo 
80 
D0005  oooooooo 
00
  M0024 ooooo1o1 
50 
  o11oo1oo 
64
  M0032 oooooooo 
A3 
D0006  1oooooo1 
81
  M0040 o1o1oooo 
82 
  ooooo1oo 
04
 
M0016 is displayed at the beginning and bit 7 changes 
to 1. (If device M23 OUT instruction comes within one 
cycle of user PLC, the sequence processing results 
will follow.) 
(Example 2) 
 
 
 
Data is not displayed in the SET DATA field at the screen top. 
 
 
 
 
 
CAUTION
 
 
  
 
 
When forcibly setting (forcibly outputting) data on the I/F diagnosis screen during machine 
operation, pay careful attention to the sequence operation. 
 
 (Note)  An input signal (X or U) to the PLC is updated at the beginning of each cycle of the PLC. Therefore, 
the signal, once forcibly defined in single-shot type mode, is restored after one cycle.