7.  Diagnosis 
7.6  Adjustment 
 
 
 
I-293 
7.6  Adjustment 
 
 
Pressing the menu key 
 
 
ADJUST 
 displays the ADJUST S-ANALOG screen. 
 
 
ABS-SRV
ADJUST
HISTORY CMPOSIT  MENU 
 [ADJUST S-ANALOG] 
ALARM/DIAGN 6 
 
INPUT : SET START / FIN 
 # 
: HIGHER VOLTAGE
 100 
AUTO ADJUST
   
: LOWER VOLTAGE
 
 101 ch0  offset 
120 
107 ch2 
offset 
0
 102 
+gain 
-55 
108 
+gain 
0
 103 
-gain 
-55 
109 
-gain 
0
 104 ch1  offset 
  0 
110 ch3 
offset 
0
 105 
+gain 
  0 
110 
+gain 
0
 106 
-gain 
  0 
112 
-gain 
0
 
 TEMP. DATA : 
  
EXECUTING AUTOMATIC ADJUSTMENT 
 #(100) 
 
 
7.6.1  Adjustment Preparation 
 
 
(1)  The PLC must be stopped before adjusting the S-analog output.  
 
 
The following two methods can be used to stop the PLC. 
 
 
1)  Stopping with rotary switch 
 
 
 
Set the rotary switch NCSYS on the bottom of the unit to 1. 
 
 
2)  Stopping with PLC onboard 
  
 
Press 
the 
 
 
F0 
 
 
MENU 
 
 
FILE 
 and 
 
RUN/ 
STOP 
 keys, and input "1". 
 
(2)  Select the ADJUST S-ANALOG screen. 
  
Press 
the 
   
DIAGN 
IN/OUT
 
 
 
MENU 
 and 
 
 
ADJUST 
 keys. 
 
 
7.6.2  Automatic Analog Output Adjustment 
 
 
Select #100 to execute automatic adjustment. 
 
→ "AUTO ADJUST" will be highlighted, and the message "EXECUTING AUTOMATIC ADJUSTMENT" will 
display. 
 
Automatic adjustment will execute offset adjustment and +gain adjustment for the remote I/O analog 
outputs (max. 4ch) connected to the main unit. The 
−gain will be handled as the +gain. 
 
After adjustment is completed, the message "AUTOMATIC ADJUSTMENT COMPLETE" will display, and 
the "AUTO ADJUST" item will return to the normal display.