Справочник Пользователя для Mitsubishi Electronics 13JW55

Скачать
Страница из 350
 
 
4 - 14
 
 
 
4.5  
PLS 
  Pulse (turns on the specified device for one scan at rising edge of an input condition.) 
 PLF    Pulf (turns on the specified device for one scan at falling edge of an input condition.) 
Project name 
QB-5 
Program name 
MAIN 
 
 
0
3
X0
X1
PLS
M5
PLF
M0
1
2
 
 
1
  • The PLS instruction turns on the specified device only for one scan when the
execution command is turned on from off. 
 
[Timing chart] 
 
X0
M5
One scan
One scan
 
 
2
  • The PLF instruction turns on the specified device only for one scan when the
execution command is turned off from on. 
 
[Timing chart] 
 
X1
M0
One scan
One scan