7.5.3    List of I/O signals and buffer memory assignment 
(1)  List of I/O signals 
The following shows a list of the I/O signals for the A/D converter modules. 
Note that I/O numbers (X/Y) shown in this section and thereafter are the values 
when the start I/O number for the A/D converter module is set to 0. 
 
Signal direction: CPU 
← A/D converter module 
Signal direction: CPU 
→ A/D converter module 
Device No. (input) 
Signal name 
Device No. (output)
Signal name 
X0 Module 
READY 
Y0 
X1 
Temperature drift compensation flag 
Y1 
X2 Y2 
X3 Y3 
X4 Y4 
X5 Y5 
X6 Y6 
X7 
Use prohibited
*1
 
Y7 
X8 
High resolution mode status flag 
Y8 
Use prohibited
*1
 
X9 
Operating condition setting 
completed flag 
Y9 
Operating condition setting 
request 
XA 
Offset/gain setting mode flag 
YA 
User range writing request 
XB 
Channel change completed flag 
YB 
Channel change request 
XC Use 
prohibited
*1
 YC 
Use 
prohibited
*1
 
XD 
Maximum value/minimum value reset 
completed flag 
YD 
Maximum value/minimum 
value reset request 
XE 
A/D conversion completed flag 
YE 
Use prohibited
*1
 
XF 
Error flag 
YF 
Error clear request 
 
POINT  
*1: These signals cannot be used by the user since they are for system use only.   
If these are turned on/off by the sequence program, the functioning of the A/D 
converter module cannot be guaranteed.