Справочник Пользователя для Mitsubishi Electronics 13JW55

Скачать
Страница из 350
 
 
9 - 3
 
 
 
(2) Periodic 
inspection 
The following table lists the items that must be inspected one or two times every 
half year to a year. When the equipment has been relocated or modified, or 
wiring layout has been changed, perform this inspection. 
 
Table 9.2 Periodic inspection 
Item
Inspection item 
Inspection contents
Judgment criterion 
Measures 
Ambient 
temperature 
0 to 55 °C 
Ambient humidity
5 to 95% RH
*1
 
1
Ambient environment 
Ambience 
Measure the 
temperature and 
humidity with a 
thermometer and a 
hygrometer. 
Measure corrosive gas. Corrosive gas must not 
be present. 
When the 
programmable 
controller is used in the 
board, the ambient 
humidity in the board is 
the ambient humidity. 
85 to 132VAC 
2
Power supply voltage 
Measure the voltage 
across the terminals of 
100/200VAC. 
170 to 264VAC 
Change the power 
supply. 
Looseness, rattling
Move the module to 
check for looseness and
rattling. 
The module must be 
installed securely. 
Retighten the screws. 
If the CPU, I/O, or 
power supply module is 
loose, fix it with screws.
3
Installation  Adhesion of dirt 
and foreign matter
Check visually. 
Dirt and foreign matter 
must not be present. 
Remove and clean the 
dirt and foreign matter.
Looseness of 
terminal screws 
Retighten screws with a 
screwdriver. 
Screws must not be 
loose. 
Retighten the terminal 
screws. 
Distance between 
solderless 
terminals 
Check visually. 
The proper distance 
must be provided 
between solderless 
terminals. 
Set the proper distance.
4
Connection conditions 
Looseness of 
connectors 
Check visually. 
Connectors must not be 
loose. 
Retighten the connector 
fixing screws. 
5
Battery 
Check that SM51 or 
SM52 is turned off with 
GX Works2. 
(Preventive 
maintenance) 
Even if the lowering of a 
battery capacity is not 
displayed, replace the 
battery with a new one if
the specified service life 
of the battery is 
exceeded. 
6
Spare product 
Install the product on 
the actual 
programmable 
controller and check the 
operation. 
The operation must 
meet the specifications. 
Use the normal product 
on the actual 
programmable 
controller as a spare 
product. 
7
Check the stored 
program 
Compare the stored 
program with the 
running program. 
The two programs must 
be identical. 
Correct if any difference 
is found. 
8
Fan (heat exchanger) 
filter 
Rotation status 
Rotation sound 
Clogging 
The fan must rotate 
without abnormal 
sounds. 
The fan must rotate 
without clogging. 
Replace if any error is 
found. 
Clean. 
9
Analog I/O 
Check the offset/gain 
value. 
The value must be 
identical with the 
specifications (design 
value). 
Correct if any difference 
is found. 
*1:  When AnS Series Module is used in the system, the judgment criteria will be from 10 to 90% RH. 
 
9.3  Consumable Product 
Backup batteries on programmable controllers are consumable products.