Справочник Пользователя для Mitsubishi Electronics 13JW55

Скачать
Страница из 350
 
 
9 - 7
 
 
 
9.6  Using Support Equipment 
The following shows examples of support equipment in which programmable 
controller-used systems or devices automatically notify a detected failure or 
operation status to an operator or maintenance personnel during an automatic 
control operation. 
 
1. 
Displaying an error using a commercial lamp
 
Connect the error lamp to the output module of the programmable controller so 
that the lamp flashes when an error is detected. 
 Lamp flicker   
Output module (Y50 to Y6F)
Error indication lamp
Control panel
The lamp (Y50) flashes 
when an error is detected.
SM1
Y50
SM412
(Error detection)
(1-sec. clock)
 
 
2. 
Displaying an error code on a commercial digital display
 
Connect the digital display to the output module of the programmable controller 
so that the error code number of the detected error is indicated on the digital 
display. 
 Numerical display   
Output module (Y70 to Y8F)
The error code number is 
displayed on the digital display 
when an error is detected.
SM1
(Error detection)
Error indication lamp
Control panel
Error code
BCD
SD0
K2Y70
0
0
Error code
3
2
(Error code)
 
 
NOTE 
 
The above programs cannot be executed when a stop error occurs.