Hardware Maintenance Manual: IBM PC Server/Enterprise Racks
 
 
Figure 71. Routing the fixed line cord and power cables
5.
Route the line cord towards a dedicated power source.  Use the provided cable 
straps to secure the line cord along the way.  Use the openings in your rack 
cabinet, if you must exit the rack cabinet to connect to your power source.
6.
After you connect the line cord to a properly wired and grounded dedicated 
power source, you can connect up to three other M/PDU family devices to the 
three power outlets on the Rack PDU.  Route all other power cables neatly, and 
use the provided cable straps to secure the cables that you plug into the outlets on 
the Rack PDU.
Installing two devices vertically
Use the following procedure to mount two Rack PDUs in the side of your rack 
cabinet:
Note:
The mounting holes on the upper and lower side braces in a rack side 
compartment must be between 48.6 cm (19.1 in.) and 56.9 cm (22.4 in.) apart.  If 
your rack cabinet has movable side braces, refer to your rack documentation 
for information about relocating your side braces if they are not already spaced 
for this installation.