6.1 Technical characteristics
Rating
AC input
 Voltage
 Frequency
 Power factor
Output
 Voltage
 Frequency
 Harmonic distortion
 Overload capacity
Battery
Environment
 Noise level
 Operating temperature
 Relative humidity
Standards and certification
 Safety
 Performance
 EMC
 Marking
Pulsar EXtreme 2200C
2200 VA / 1540 W
Pulsar EXtreme 3200C
3200 VA / 2080 W
Single phase, 120 V / 140 V / 160 V to 284 V 
(1)
50/60 Hz (auto-selection)
 0.95
Single phase, 230 V 
±
 3% 
(2)
50/60 Hz 
±
 5% 
(3)
< 4% for linear loads, < 6% for non-linear loads
110% continuous, 130% for 12 seconds, > 130% for 1.5 seconds
6 x 12 V - 7 Ah,
sealed lead-acid, maintenance free
6 x 12 V - 9 Ah,
sealed lead-acid, maintenance free
< 50 dBA
0 to 40
°
C
20 to 90% (without condensation)
IEC/EN 62040-1-1, EN 60950-1 (RD)
IEC/EN 62040-3
EN 50091-2/IEC 62040-2 class B
IEC 61000-4-2/-3/-4/-6-8/-11, IEC 61000-3-2/-3
CE, TÜV/GS, UL, cUL, CB report
(1) Values indicated for 33%, 66% and 100% of UPS rated output.
(2) Adjustable from 200 V to 250 V using UPS Driver software.
(3) Frequency-converter mode can be set using the UPS Driver software.