3400723100/AD
Troubleshooting requiring MGE UPS SYSTEMS after-sales support
4. Maintenance
4.1 Trouble-shooting
Indication
LED  17  goes ON and
the buzzer sounds 
continuously.
Signification
UPS electronics have detected a UPS fault.
The connected equipment is no longer supplied.
The equipment connected to the UPS is no 
longer protected.
Correction
Call the after-sales support 
department.
Indication
LED  18  flashes and the
buzzer beeps once.
LED  17  flashes.
Signification
UPS overload. The power drawn by the connected 
equipment exceeds UPS capacity.
A battery fault was detected during the automatic bat-
tery test.
Correction
Check the power drawn by the 
equipment and disconnect any 
non-priority devices.
Replace the battery module 
(see section 4.2).