Справочник Пользователя для Minuteman UPS ALLIANCE

Скачать
Страница из 15
 
 
 
 
 
Input Voltage (AC Mode Function) 
95-135 VAC (w/ boost) 
                             120 VAC Models 
      
102-135 VAC (w/o boost) 
175-260 VAC (w/ boost) 
                              220 VAC Models 
190-260 VAC (w/o boost) 
Boost Capability (AC Mode Function) 
+ 12 % 
5VAC per SW, (120VAC models) 
Transfer Voltage Adjustment 
10VAC per SW (220VAC models) 
Transfer Time 
2 msec typical 
Input Frequency Deviation for Synchronization 
± 10 % 
Inrush Current 
1.5x rated 
Surge Protection 
3 way, meets IEEE STD. 587 
RFI/EMI Filtering 
Both Common and Normal Modes 
Inverter mode (Backup Operation) 
Synchronized Simulated 
     Waveform 
Sinewave Approximation 
     Crest Factor (Non-Linear Load) 
3:1 
     Overload Capacity (50 msec Maximum) 
3x rated 
     Voltage Regulation 
± 5% 
     Frequency Regulation 
± 1% 
     DC-to-AC Efficiency (Full Load) 
75% 
     Overload/Short Circuit Protection 
Electronic and Fused 
     Discharged Battery Recharge Time 
8 hours (95% of full charge) 
     Run Time 
See Chart