Справочник Пользователя для Emerson 210-2002

Скачать
Страница из 5
             
 
 
 
Wall-Mounted Dewpoint Sensor 
Product Information Sheet
 
210-2002
       Input Status Screen
 
Figure 1 - Sensor and Input Board Wiring
 
Overview 
The 210-2002 is a Vaporstat™ wall-mounted 
dewpoint sensor. The sensor is designed for 
measuring indoor or outside dewpoint or absolute 
humidity level.  
 
Sensor Wiring 
 
1. For wiring the dewpoint sensor to a CPC 
input board, use Belden #8761 shielded two-
conductor cable or equivalent. 
 
2. Connect the BLACK and WHITE wires to the 
screw terminals on the sensor’s connector as 
shown in 
Figure 1 (connect BLACK to Signal 
Ground and WHITE to 0-5V Output). Clip the 
SHIELD wire. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
3. Connect the SHIELD and BLACK wires to the 
0V terminal of the input board. Connect the 
WHITE wire to the SIG terminal of the input 
board. 
 
4. Connect 24VAC (a separate 120VAC/24VAC 
transformer must be used P/N 640-0039) to 
the power terminal on the dewpoint sensor 
back plate using the BLACK and WHITE wires. 
(This 24VAC transformer must only be used 
to power this dewpoint sensor. Do not use 
this transformer to power additional 
devices.) 
 
5. Locate the input dip switch for the sensor 
point, and set to the OFF position (LEFT for 
MultiFlex, DOWN for 16AI). Refer to the input 
board’s user manual for locations of the 
input dip switches. 
Controller Setup 
 
NOTE:  DO NOT set this sensor up with a sensor type 
of “Dewpoint”; that setting is only for CPC 
Dewpoint Probes (P/N 203-1902). This 
dewpoint sensor MUST be set up as a linear
 
 
sensor type. 
E2/Einstein 
 
1. After logging  into the   controller,   press                                    
6
 + 
 to open the Input Status screen or 
press the 
I
 key, 
 (System 
Configuration), 
 (Input Summary). (If 
using an Einstein, press F8(ACTIONS) from 
the  Home screen.  Press Y (System  Setup).   
Press 6 (Input and Output Point Setup).  
Press 1 (Input  Summary) to open the Input 
Summary screen.) 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 