APPENDIX 7    CABLE MANUFACTURING DRAWINGS 
Appendix 7.14    FCUA-R211 Cable Manufacturing Drawing 
 
 
I - 99 
Appendix 7.14  FCUA-R211 Cable Manufacturing Drawing 
 
Application: 
Control unit – remote I/O unit connection 
Remote I/O unit – remote I/O unit connection 
Remote I/O unit – communication terminal connection
 
Option (Compatible connector set) 
FCUA-CN211 
(Note that when a one end connector 
and contact are used, there is no 
crimp terminal) 
 
List of parts used 
 
1  2 
4
1
2
R211 
 
R211 
Control unit side 
Note (3)
Assembly drawing 
No.
Part name/type 
Maker 
Qty.
Connector 
1-178288-3 
Tyco 
Electronics 
AMP 
Contact 
1-175218-2 
Tyco 
Electronics 
AMP 
Wire material 
MIX3CHRV-SV-SB 
Twisted pair cable 
with compound 
3-pair shield. 
Note (1) 
TOA 
Electric 
Industry 
(1)
Crimp terminal 
V1.25-3 
J. S. T 
Crimp terminal 
V1.25-5 
J. S. T 
 
 




TXRX 
TXRX* 
LG 
FG 
Note (5) 
TXRX 
TXRX* 
LG 
FG 
Maximum cable length: 50m
Connection diagram 
 
 
Manufacturing precautions 
(1)  The wire material shall be a shielded 3-pair stranded pair cable equivalent to AWG20 (0.5mm
2
). 
(2)  The parts used shall be Mitsubishi recommended parts. Equivalent parts may be used providing 
they are compatible with the specifications. 
(3)  Attach the nameplate (with protective cover stamped with the cable name) in the position 
designated in the assembly drawing.   
(4)  Install each crimp terminal side after stamping the name of each signal on the mark tube. 
(5)  Protect both ends of the wire material with insulation bushing. 
(6)  Use AWG18 (0.75mm
2
) or equivalent for the shield treatment wire material. 
(7)  Ground the crimp terminal connected to the shield to the control unit or communication terminal 
frame ground. 
Note that there may be cases where only one end is connected, both ends are connected, or 
neither end is connected to improve the noise resistance,.