APPENDIX 9    EMC INSTALLATION GUIDELINES 
Appendix 9.6    Parts for EMC Countermeasures 
 
 
I - 119 
Appendix 9.6.4    Selection of stabilized power supply 
 
Consider the following characteristics when selecting the stabilized power supply (prepared by user). 
Use a power supply that complies with CE Marking or that follows the Safety Standards given below. 
 
 
Stabilized power supply selection items 
Item
 
 Conditions 
Voltage fluctuation
±5% 
±5% or less of 24VDC output 
Ripple noise 
Max. 120mV
±5% or less of 24VDC output 
Output 
Spike noise 
Max. 500mV
 
Output current 
– 
Refer to the Connection Manual and 
calculate. 
Output holding time 
Min. 20ms 
Instantaneous OFF time 
 
 
Standards 
Safety Standards 
:  UL1950, CSA C22.2 No. 234 approved, IEC950 compliant 
Noise Terminal Voltage 
:  FCC Class A, VCCI-1 Class 
High Harmonics Current Restrictions :  IEC1000-3-2