4. CONTROL UNIT CONNECTIONS 
4.5  Connecting the Sensor Signal (skip) 
 
 
I - 24 
4.5  Connecting the Sensor Signal (skip) 
 
The SKIP connector is used to connect the sensor signal (skip). 
The sensor signal is used for high-speed signal processing, so take special care to prevent noise 
induction, etc., from occurring. If the cable is long, always use a shielded wire. 
Note that the input conditions, such as the input signal holding time, differ from the machine input/output 
signal's input conditions. 
 
 
C6/C64 control unit 
FG 
SKIP 
SKIP 
Control unit
LED1 
F340 cable 
Input circuit 
24VDC(+) 
0V 
FG 
Stabilized 
power supply 
1
 
5
 
6
 
9
 
SKIP 
connector 
pin No. 
SK
IP
Control circuit 
SKIP IN0 
SKIP IN2 
SKIP IN3 
SKIP IN1 
2.2k
Ω
2.2k
Ω
2.2k
Ω
2.2k
Ω
 
 
Input conditions 
1  Input voltage when external contact is ON 
18V or more 
2  Input current when external contact is ON 
9mA or more 
3  Input voltage when external contact is OFF 4V or less 
4  Input current when external contact is OFF
1mA or less 
5  Input signal holding time (Ton) 
2ms or more 
6  Internal response time 
0.08ms or less
7  Machine side contact capacity 
30V or more, 
16mA or more
 
+24V 
GND
Ton 
Ton 
 2ms 
t
 
 
 
 
 
 
 CAUTION 
 
  Do not apply a voltage other than that specified in this manual onto the connector. Failure 
to observe this could lead to rupture or damage. 
 
  Incorrect connections could cause device damage, so always connect the cables to the 
designated connectors. 
 
  Do not connect or disconnect the connection cable between each unit while the power is 
ON.