CONNECTION OF REMOTE I/O UNIT 
6.4  Connection of Remote I/O Power Supply 
 
 
I - 
58
 
6.4  Connection of Remote I/O Power Supply 
 
24VDC(+) is required to run the remote I/O unit. Prepare a stabilized power supply that satisfies the 
following conditions. 
 
Output voltage 
24VDC
±5% 
Ripple 
±5% (P-P) 
FCUA-DX10 
†
2.4A or more 
FCUA-DX11 
†
3.8A or more 
FCUA-DX12 
†
3.8A or more 
FCUA-DX13 
†
3.4A or more 
  Max. output  
  current 
FCUA-DX14 
†
3.4A or more 
 
The 24VDC(+) power for the control circuit is supplied from the DCIN connector on the bottom of the unit 
or from DI-L, DI-R, DO-L or DO-R connectors on the front. When supplying from the front connector, 
supply to all corresponding pins.  
When manufacturing the R300 cable, use the CN300 one end connector (optional, with one end), and 
when manufacturing the R301 cable, use the CS301 connector set (optional, with both ends). 
 
 
Remote I/O unit 
DI-L DI-R
Machine control panel, 
electric cabinet, etc. 
R300 cable
or 
R301 cable
Supply to either method 
DI-L
 
<Connection outline> 
Front 
(Front)
(Back)
Bottom
DO-L DO-R
DI-R
DO-L DO-R
24VDC(+)
 
0V
DCIN 
24VDC(+) 
0V 
FG 
1
2
3
 
B1 
B2 
A1 
A2 
B1 
B2 
A1 
A2 
PL 
RA 
24VDC(+)
 
FG 
0V 
R220 cable 
Stabilized power supply 
(Prepare separately) 
FG 
Y
Y
 
B1
B2
A1
A2
B1
B2
A1
A2
 
 CAUTION 
 
 
Do not apply voltages other than those indicated in this manual on the connector. Doing 
so may lead to destruction or damage.
 
 
 
Incorrect connections could damage the device, so always connect the cable to the 
designated connector.