Листовка для Panasonic EBL128

Скачать
Страница из 2
 
All technical features and data are subject to changes without notice, resulting from continuous development and improvement. 
Product Leaflet 
Date of issue 
Revision / Date of revision  
MEW00503 2006-04-04 2 
2007-01-29 
 
Type numbers 
4550 
EBL128 c.i.e. (128 addresses).  Batteries are not included. 
4552 
RS485 transceiver component, for up to four display units, i.e. Ext. Fire Brigade 
Panels 1826 / 1828, Ext. Presentation Unit 1728 and/or Alert Annunciation Units 
1735 / 1736. 
4551 
Expansion board holder.  (For two 4580 and two 4581 expansion boards.) 
4580 
8 zones expansion board.  (Max. two per c.i.e.) 
4581 
8 relays expansion board.  (Max. two per c.i.e.) 
The 4580 board can be used to connect conventional detectors and manual call points to 
EBL128.  An end-of-line capacitor (470 nF) shall be connected in the last alarm point on each 
zone line. 
More information is available in the EBL128 Planning Instructions & Operating Instructions. 
 
Technical data 
Voltage 
  primary  (V AC) 
  secondary  (V DC) 
    normal 
    by battery backup 
 
230 
 
24 
21 - 30 
Current consumption (mA) 
Depending on connected units, etc. See EBL128 Planning Instructions. 
Ambient temperature (
°C) 
  Operating 
  storage 
 
-5 to +40 
-40 to +75 
Ambient humidity (% RH) 
max. 95, non condensing 
Ingress Protection rating (estimated) 
IP32 
Inputs 
1 COM loop for 128 addresses 
 
1 programmable input  (NO / NC).   R>200Ω = open circuit.  Max. 2 mA 
Outputs 
1 programmable supervised voltage output (24 V DC, max. 500 mA)  
 
1 programmable supervised voltage output (24 V DC, max. 200 mA)  
 1 
programmable 
relay output. 
3
  Default set for routing equipment (Fire 
brigade tx).   
 
1 non-programmable relay output. 
3
  For routing equipment (Fault tx). 
 
Power supply (24 V DC, max. 200 mA) for routing equipment  
2
 
 
Power supply (24 V DC, max. 500 mA) for external equipment (Web-
server, up to 4 ext. FBPs, etc.)    Web-server requires approx. 65 mA.  
1
 
Interfaces 
RS232 ("D" connector) for a PC (Win128) 
 
RS232 for a Web-server 1588 
 
Socket for an optional RS485 transceiver, for ext. FBPs, EPUs and/or 
AAUs. 
Size H x W x D (mm) 
511 x 416 x 123 
Weight (kg) 
12.2   (Excl. Batteries) 
Colour (metal cabinet) 
Aluminium & light grey (NCS S1500-N, PMS Cool Grey 2)  
Approvals 
CE;  EN54 parts 2 & 4.  The front is fully SS3654 compliant. 
Note!  All voltages are nominal.  For more information see EBL128 Planning Instructions MEW00508. 
1
  Continuous 500 mA, 620 mA during 30 ms. 
2
  Continuous 200 mA, 240 mA during 110 ms. 
3
  Relay contacts:  max. 1 A @ 30 V DC.