II. General Information
A. Sequence of Operation
Five minutes after 
defrost heater off
1. Compressor on
2. Condenser fan on
Five minutes after 
compressor start-up
1. Evaporator fan on 
Eight minutes (freezer) or 
one minute (refrigerator) 
after evaporator fan 
start-up "dF" no longer 
displayed, cabinet temp. 
displayed
Board Self Check
1. Frame heaters on (0.3A)
2. Evaporator fan on
POWER ON
3 Minute Delay
1. Compressor start-up
2. Condenser fan start-up
Cycle Off (Cut-out 
temperature reached) 
[Minimum 3 minutes]
1. Compressor off
2. Condenser fan off
Continue as 
normal cycling
Cycle On (Cut-on 
temperature reached) 
[Minimum 3 minutes]
1. Compressor start-up
2. Condenser fan start-up
Defrost End
Defrost thermistor 
reaches defrost 
termination temperature 
[refrigerator = 68°F 
(20°C) 
4.1 k
Ω
; freezer 
= 95°F (35°C) 1.2
 kΩ
], 
or defrost timer reaches 
1 hour
1. Defrost heater off
2. Drain tank heater on         
    (thermostatic cut-off)
Defrost Start
Preprogrammed time interval
1. Compressor off
2. Evaporator fan off
3. Condenser fan off
4. Defrost heater on (1.9A)
5. "dF" displayed
Note:  
1) Cut-on, cut-off, and cabinet temperature are read by the same sensor, called the 
"cabinet thermistor." 
2) The defrost thermistor reads the evaporator temperature.
3) The drain tank heater stays on until the drain tank thermostat is satisfied. If the 
thermostat is satisfied within the first five minutes, the heater will continue to cycle 
on and off until the thermostat is satisfied past the five minute mark.
4) The evaporator fans turn off when the door is opened.