7. Module protection (H5):
Handling method:
Check if the voltage between power module P and N is too low and
if the current is too high. In normal condition, voltage between P and
 N should be about 320V.
Normal
Abnormal
Check power supply circuit of outdoor unit (if PTC resistance
rectifying bridge, reactor, capacitance etc. is ok).
Temperature of power module is too high, 
which  causes overheating protection
Protection is still displayed
Confirm the setting status of outdoor unit (cooling)
Normal
Confirm if outdoor fan motor is running; unplug the 
three connecting wires between U, V, W of compressor 
and power module. Turn on the unit to see if outdoor 
fan runs normally (about 1 minute)
Outdoor fan stops 
Measure the voltage of outdoor
fan connector
No voltage
Normal voltage 
Replace the fan
Replace the mainboard 
motor
of outdoor unit
Check if radiating paste is spread 
evenly or radiating sticker is stuck
 well; if screws of power module 
is tightened
 Reinstall power module and 
 re-spread radiating paste or 
stick radiating sticker on the
 radiator of power module.
Poor radiation, heat exchanger
 is dirty
Remove obstructions 
and clean
Outdoor fan runs 
Confirm if there is voltage output and balance of 
voltage between any two phases of U, V and W. 
Yes
No
Whether module type 
Replace the power module 
is correct
Normal
Abnormal
Normal
Abnormal
Measure the three-phase 
Replace the module 
with correct type
resistance of compressor
Replace the 
Whether cylinder of 
compressor is stuck 
compressor
If the unit runs normally after connected 
with the new compressor for trial run, the 
 cylinder of original compressor is stuck 
42