Figure 3.    Fireplace Locations and Space
                    Requirements
Clearance Requirements
The top, back, and sides of the fireplace are
defined by stand-offs.
Minimum Clearances from the Fireplace to
Combustible Materials
Glass
Back of
Metal  Ends
Top of
Sides
Floor
Fireplace
of  Fireplace
Fireplace
Ceiling
36 inches
0
1/2 inch
1/2 inch
4-1/2 inches
36 inches
(914 mm)
(13 mm)
(13 mm)
(114 mm)
(914 mm)
The clearance to the ceiling is measured from the top
of the unit, excluding any standoffs (see Step 10
Finishing).
The minimum clearance to a perpendicular wall
extending past the face of the fireplace is one inch
(25mm).
The metal end(s) of these fireplaces may NOT be
recessed into combustible construction.
3
Installing the
Fireplace
Step 1
Locating the
Fireplace
The diagram below shows space and clearance
requirements for locating a fireplace within a room.
9
Heat & Glo  •  ST-42TVFL-IPI  •  455-902 Rev. C  •  12/07
36"
GLASS
GLASS
1"
TOP
VIEW
36"