Troubleshooting 
Introduction 
Revision 6 
  HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 
105 
7/07  
 
 
 
Troubleshooting 
Introduction 
Troubleshooting procedures can be followed when inaccurate or faulty actuator operation is detected.  In 
this section, troubleshooting procedures consist of a few simple flow charts to test for proper function of 
various actuator components.  Component replacement is at the PWA or assembly level.   
Table 39 indicates some of the observable symptoms of failure that can be identified by noting the faulty 
actuator operation.  
  
Table 39 Observable Symptoms of Failure 
Symptom 
Procedure 
No Actuator current output. 
 
Replace CPU Assembly 
No Actuator slidewire output. 
 
Replace CPU Assembly 
Local display does not light. 
 
See Figure 42 
Actuator fails one or more power up diagnostics. 
 
See Figure 43 
Actuator motor does not drive in response to input signal. 
 
 
Perform input calibration.  
See Figure 42  
Actuator motor does not drive to proper position. 
 
Perform motor calibration.  
Actuator Motor is “Hunting”   
(Motor does not drive to a position and stop.) 
Process control loop is not tuned correctly. 
Refer to the Instruction Manual for your 
controller on how to tune a loop. 
Increase the Deadband in the Actuator 
and/or in the control loop. 
Position sensor position is not correct. 
 
See page 85. 
Auto/Manual Switch does not operate correctly. 
 
See Figure 45 
Relay(s) does not operate. 
 
See Figure 46