T8775A,C THE DIGITAL ROUND™ NON-PROGRAMMABLE THERMOSTATS
3
69-1677EF—1
CUSTOMIZE THERMOSTAT
Setting Fuel Switch (T8775C only)
The fuel switch is preset at the factory in the F 
position. See Fig. 7. This is the correct setting for gas 
or oil systems. If the T8775C is being installed on an 
electric heat system, or a heat pump, set the switch to 
the E position. The E setting allows the fan to turn on 
immediately with the heating equipment in a system 
where the G terminal is connected.
Fig. 7. Fuel switch.
DIP Switch
To adjust the heat cycle rate or the Fahrenheit/Celsius 
indication, locate DIP switch 1, 2 and 3 on the back of 
the thermostat. See Fig. 8. 
Fig. 8. DIP switch.
Set Heat Cycle Rate
Use DIP switches 1 and 2 to set the heat cycle rate. 
See Table 1.
Table 1.  Heat Cycle Rate.
Fahrenheit/Celsius Indication
Use DIP switch 3 to set the desired temperature 
indication. See Table 2. 
Table 2. Temperature Indication.
Mounting Thermostat to Wallplate
Fig. 9. Mounting thermostat to wallplate.
OPERATION
Setting SYSTEM and FAN Switches 
(T8775C only)
System and fan settings are controlled manually by 
using the switches located at the top of the 
thermostat. See Fig. 10.
M19497
FUEL SWITCH
ON
1
2
3
M19567
BACK OF THERMOSTAT
DIP SWITCH
Heating System
Cycles 
Per 
Hour
DIP 
Switch 
1
DIP 
Switch 
2
Steam, Gravity
1
On
On
High Efficiency Warm Air 
(90%+ efficiency), Hot Water, 
Heat Pump
3
Off
On
Gas or Oil Warm Air (factory 
setting)
6
Off
Off
Electric Warm Air
9
On
Off
In Floor Radiant Heat
Check with manufacturer 
for recommended cycle 
rate.
Fahrenheit/Celsius 
Display
DIP Switch 3
Fahrenheit (factory setting) Off
Celsius
On
M19498
ENGAGE TABS 
AT BOTTOM OF 
THERMOSTAT 
AND WALL PLATE.
PRESS UPPER
EDGE OF CASE