R7500C WIDE RANGE PROPORTIONAL TEMPERATURE CONTROLLER  
WIRING 
All wiring must agree with local electrical codes and  
ordinances.  
Since the Controller circuits are rated NEC Class 2, some  
local codes allow open (no conduit) wiring.  
Number 18 gage 1.0 mm insulated wire or two- or three­
conductor thermostat cable is acceptable for use with these  
Controllers, except on long sensor or remote setpoint  
potentiometer runs where a larger wire size should be used.  
See Table 1.  
All control wiring connections to the Controller are made to  
the 6-inch (152 mm), color-coded leadwires found bundled  
under the cover. There are two orange wires to facilitate  
connections to the converter and/or sensors.  
Crimp type connectors are recommend for field connections  
of the control wiring. Refer to job drawings for specific wiring  
information. See Figures 2 through 4 for some typical  
wiring diagrams.  
IMPORTANT  
Observe color-coding of wires when making connections.  
R7503
BALCO 
CONVERTER 
Table 1. Wire Resistance, Ohms per 1,000 Feet (304m). 
Wire Gage 
Wire Dia. 
Size (mm) 
Ohms/1000 ft 
(304 m) of Wire 
18 
1.00 
6.5 
16 
1.25 
4.0 
14 
1.60 
2.6 
12 
2.00 
1.6 
10 
2.50 
1.0 
When determining proper wire size, remember there are two 
wires to the sensor and the setpoint potentiometer. Double 
the distance to the sensor or potentiometer to obtain the 
proper wire length. Calibration of the controller will be 
offset approximately 1F (0.5C) for every one ohm of lead 
wire resistance. 
BALCO MAIN SENSOR 
MAIN SENSOR 
BLACK 
ORANGE 
ORANGE 
YELLOW 
VIOLET 
POWER 
BROWN 


R7500 
BALCO COMPENSATION 
SENSOR 
BOTH ORANGE WIRES ARE ELECTICALY IDENTICAL.
OPTIONAL DISCHARGE COMPENSATION SENSOR. 
SUBSTITUTE WITH 500 OHM RESISTOR WHEN 
COMPENSATION IS NOT USED. 
C7828 
Fig. 2. Typical Hookup Diagram of R7500C Model with  
Integral Setpoint Adjustment.  
NOTE:   When the compensation sensor is not used, 
substitute a 500-ohm resistor and set the 
compensation ratio at the maximum setting (20). 
M734K 
M745J 
14002385-008 
REMOTE 
SETPOINT 
ADJUST 
BLK 
ORN 
ORN 
YEL 
VIO 
POWER 
BRN 




R7500
270
Ω 
CONNECT Z-D FOR DIRECT ACTION; Z-R FOR 
REVERSE. 
OPTIONAL DISCHARGE COMPENSATION SENSOR. 
SUBSTITUTE WITH 500 OHM RESISTOR WHEN 
COMPENSATION IS NOT USED. 
MOVE WIPER UP TO RAISE SETPOINT. 
BOTH ORANGE WIRES ARE ELECTRICALY IDENTICAL. 
C7829 
BALCO COMPENSATION 
SENSOR 
Fig. 3. Typical Hookup Diagram of R7500C with Remote  
Temperature Selector.  
95-7205