Справочник Пользователя для Moxa PT-7324-F-HV

Скачать
Страница из 6
1
w w w. m o x a . c o m
i n f o @ m o x a . c o m
Industrial Ethernet Solutions
PT-7324 Series
Introduction
The PowerTrans PT-7324 smart Ethernet switch is designed to meet the 
demands of power substation automation systems (IEC 61850-3, IEEE 
1613), traffic control systems (NEMA TS2), and railway applications 
(EN50121-4). The PT-7324 is also equipped with smart “Class of 
Service” features suitable for multimedia applications, and port-based 
Port-based VLAN to ease network planning
IEC 61850-3, IEEE 1613 (power substations), NEMA TS2 (traffic 
 
control systems), and EN50121-4 (railway applications) compliant
Port-based VLAN to enhance security/network performance
 
802.1p priority queues, port-based QoS
 
Smart web-based management makes configuration easy
 
Universal power supply range, 12/24/48 VDC or 110/220 VDC/VAC
 
-40 to 85°C operating temperature range
 
Smart Rackmount Ethernet Switch System, PT-7324
 
Specifications
2
4
6
8
1
3
5
7
10
12
14
16
9
11
13
15
18
20
22
17
19
21
PT-7324
M1
LNK/ACT
SPEED
FAULT
STAT
PWR1
PWR2
MODE
FDX/HDX
19
1
20
2
18
22
17
21
8
7
6
5
2
1
4
3
16
15
14
13
10
9
12
11
M1
Slot 1
IEC 61850-3 22+2G-port Gigabit smart rackmount Ethernet switches
VLAN features that can be used to segment your network without 
being restricted by physical connections. If you do not want to receive 
too many broadcast packets, the broadcast storm filtering feature will 
discard broadcast packets if the number of such packets exceeds a 
threshold in a preset period of time.
Technology
Standards:  
IEEE 802.3 for 10BaseT 
IEEE 802.3u for 100BaseT(X) and 100Base FX 
IEEE 802.3ab for 1000BaseT(X) 
IEEE 802.3z for 1000BaseSX/LX/LHX/ZX 
IEEE 802.3x for Flow Control 
IEEE 802.1p for Class of Service
Flow Control: IEEE 802.3x flow control, back pressure flow control 
Switch Properties
Priority Queues: 2
Max. Number of Available VLANs: 24
Interface 
RJ45 Ports: 10/100BaseT(X) or 10/100/1000BaseT(X) auto 
negotiation speed, F/H duplex mode and auto MDI/MDI-X connection
Fiber Ports: 100BaseFX (SC/ST connector) or 1000BaseSFP slots
LED Indicators: STAT, PWR1, PWR2, FAULT, LNK/ACT, FDX/HDX, 
SPEED
Alarm Contact: 1 relay output with current carrying capacity of 3 A @ 
30 VDC or 3 A @ 240 VAC
Note: Slot 1 for a 2-port PM-7200 Gigabit Ethernet combo module, or 1 or 
2-port PM-7200 fast Ethernet module.
Power Requirements
Input Voltage:  
• 12/24/48 VDC (9 to 60 V) 
• 110/220 VDC/VAC (88 to 300 VDC and 85 to 264 VAC)
Input Current: (all ports are equipped with fiber) 
• Max. 0.68 A @ 24 VDC 
• Max. 0.35 A @ 48 VDC 
• Max. 0.17/0.11 A @ 110/220 VDC 
• Max. 0.33/0.23 A @ 110/220 VAC
Overload Current Protection: Present
Features and Benefits
Connection: 10-pin terminal blocks 
Reverse Polarity Protection: Present 
Physical Characteristics  
Housing: IP30 protection
Dimensions: 440 x 44 x 254 mm (17.32 x 1.73 x 10.00 in)
Weight: 3300 g
Installation: 19’’ rack mounting
Environmental Limits
Operating Temperature: -40 to 85°C (-40 to 185°F)
Storage Temperature: -40 to 85°C (-40 to 185°F) 
Ambient Relative Humidity: 5 to 95% (non-condensing)
Regulatory Approvals 
Safety: UL60950-1, CSA C22.2 No. 60950-1, EN60950-1 (Pending)
EMI: FCC Part 15, CISPR (EN55022) class A
Power Automation: IEC 61850-3, IEEE 1613
Maritime: DNV (Pending), GL (Pending)
Traffic Control: NEMA TS2 (Pending)
Rail Traffic: EN50155/EN50121-4
Note: Please check Moxa’s website for the most up-to-date certification status.
Warranty
Warranty Period: 5 years
Details: See www.moxa.com/warranty
802.1p priority queues and port-based QoS to increase determinism
Broadcast storm filtering