UPS Battery
Disconnect
Receptacle
UPS Battery
Connector
Cable Plug
PDU Circuit
Breakers (4)
Energize UPS Batteries
10
The UPS is shipped with the batteries pre-installed. Depending on your system
configuration, energize the batteries as outlined below.
If your system configuration
includes an External Battery
Pack, plug its Battery Connector
into the UPS battery disconnect
receptacle.
If your system configuration
DOES NOT include an External
Battery Pack, plug the UPS
Battery Connector Cable Plug
into the UPS battery disconnect
receptacle.
A.
B.
Battery
Connector
Cable Plug
Rear
Channels
Rear Channels
Rack-mount PDU
220–240 V
NetShelter VX
Expansion Enclosure
(Rear View)
Routing Rack-Mount PDUs
between Enclosures
Base Enclosure
NetShelter VX
Expansion Enclosures
Connect the Rack-Mount
Power Distribution Units (PDUs)
8
Route the power cord for each rack-mount PDU
using the holes provided on either side at the
bottom of an enclosure. Push the excess cord
into the channels next to the rack-mount PDUs
for a neater appearance.
Plug each power cord into an outlet receptacle
(IEC320 C19) on the UPS.
UPS Battery
Disconnect
Receptacle
Base Enclosure
(Rear View)
External Battery
Pack Connector
Install the Rack-Mount
Power Distribution Units (PDUs)
7
Before beginning this step, see the
for safety and
installation instructions.
Install the rack-mount PDU’s vertically in the left or
right rear channel of each applicable enclosure.
Power
Distribution Unit (PDU) User’s Manual
¡
¡
Each Enclosure contains receptacles to support
up to two 220–240 V rack-mount PDUs.
If more than two 220–240 V rack-mount PDUs
are required, daisy-chain up to two 220–240 V
rack-mount PDUs.
A complete daisy-chained 220–240 V
circuit has a 15 A current availability.
Note
¡ MasterSwitch VM PDUs may be substituted if
remotely controllable outlets are required.
Finish the Installation
11
Before beginning each step in this section, see the referenced documentation for
detailed instructions.
Make sure that the UPS is properly connected. See Step 4.
Make sure that all circuit breakers are in the ON position. See Step 6.
Start up the UPS by turning it ON and powering up the load equipment. See the
“Operation” section of the
for detailed instructions.
If applicable, change the PowerView Display language setting as outlined in the
“Language Setting” procedure in the
.
If necessary, configure the rack-mount PDUs alarm threshold as outlined in the
.
If your system includes an External Battery Pack, perform all procedures as
outlined in the “Operating the SmartUPS with a Battery Pack” section of the
.
Configure any management accessory cards and software.
Smart-UPS 5000VA 5U Rack Mount XL UPS User’s
Manual
PowerView RM User’s Manual
Power Distribution Unit (PDU) User’s Manual
Smart-UPS 3U Rack Mount External Battery Pack User’s Manual
A.
B.
C.
D.
E.
F.
G.
Troubleshooting Procedures
12
For troubleshooting procedures, see the accompanying APC product documentation.
If a system-wide problem persists, call APC technical support at 1-877-537-0607. For
individual component support, visit APC’s website at www.apc.com/support.
Ensure that Step 4 is properly completed.
Problem with an
Extended Run
Cabinet.
A circuit breaker
trips repeatedly.
Fault LEDs or
error messages.
PowerView
Display not ON.
NO power in
multiple
enclosures.
NO power in an
individual rack-
mount PDU or
one enclosure.
Perform all of the startup procedures in
the UPS user’s manual.
Ensure that the Mains circuit breaker is ON.
Ensure that Step 6 is properly completed.
A UPS PDU circuit breaker is OFF.
The rack-mount PDU is not plugged
into the outlet receptacle.
A UPS PDU circuit breaker is OFF.
The Extended Run Cabinet is not
properly connected.
The circuit breaker is overloaded.
The PowerView Display unit is not
connected to the UPS.
There is a potential system fault or
tripped alarm.
Ensure that Step 8 is properly completed.
Ensure that Step 6 is properly completed.
See the “Operating the Smart-UPS with
a Battery Pack” section in External
Battery Pack user’s manual.
Redistribute the load, then ensure that
the circuit breaker is turned ON.
Ensure that display cables are properly
connected.
See the “Operation” and “User
Configurable Items” sections of the UPS
user’s manual.
NO power in
ALL
enclosures.
The UPS is not turned ON.
VAC input is not present.
Install Optional Equipment in the Enclosures
9
Your system is now ready for you to install optional equipment. See the
documentation you received with optional equipment and accessories for their
installation and setup.
Install any optional equipment and accessories. Visit APC’s website at
www.apc.com for available PowerStruXure Type A accessories.
If you plan to manage your system using the pre-installed Web/SNMP
Management Card, connect the network cable now.
A.
B.
Batteries can be permanently damaged if installed in a system that is
not being used. Store battery module(s) at an ambient temperature
below 25 ºC (77 ºF).
Caution
Problem
Possible Cause
Solution
Connect the UPS PDU Circuit Breakers
6
Before beginning this step, see the
for
safety and detailed installation instructions.
In the Base Enclosure, set the UPS PDU Circuit
Breakers to the ON position.
Smart-UPS
5000VA 5U Rack Mount XL UPS User’s Manual
PDU Circuit Breakers
220–240 VAC 15 A
IEC320 C19
Entire contents copyright 2002-2003 by American Power Conversion Corporation. All rights reserved. Reproduction in whole or in part without permission is prohibited.
APC, PowerChute, PowerStruXure, SmartUPS and Symmetra are registered trademarks of American Power Conversion Corporation. All other trademarks are the property of their respective owners.
©
990-1406-002, English, October 2002
16
w
ww
.a
pc.
co
m
M
etered
Di
strib
ution
Power
U
nit
®
Li
ne
Pre
ss
to
m
ute
the
ala
rm.
Pre
ss
for
10
second
s
to
inve
rt
the
dis
pla
y.
Amps
Amps
Base Enclosure
(Rear View)
16
ww
w.
a
p
c.com
M
etere
d
Di
stri
but
io
n
Po
we
r
Unit
®
Lin
e
Pr
es
s
to
m
ut
e
th
e
ala
rm.
Pr
ess
for
10
se
co
nd
s
to
in
ve
rt
th
e
displa
y.
Amps
Amps
Rack-Mount
PDU Cable
and Plug
IEC320 C19 (4)
Base Enclosure
(Rear View)
UPS PDU
Base Enclosure
(Rear View)
UPS PDU