1
w w w. m o x a . c o m
i n f o @ m o x a . c o m
Industrial Ethernet Gateways
1, 2, and 4-port standard Modbus gateways
Specifications
Overview
High Density, Cost-effective Gateways
Standard Modbus Network Integration
MGate™ MB3180/3280/3480
The MB3180, MB3280, and MB3480 are standard Modbus gateways 
that convert between Modbus TCP and Modbus RTU/ASCII protocols. 
Up to 16 simultaneous Modbus TCP masters are supported, with up to 
The three standard MGate™ models (MB3180, MB3280, and MB3480) 
are designed for easy integration of Modbus TCP and RTU/ASCII 
networks. With these models, Modbus serial slave devices can be 
seamlessly incorporated into an existing Modbus TCP network, and 
The MGate™ MB3000 gateways can effectively connect a high density 
of Modbus nodes to the same network. The MB3280 can manage 
up to 62 serial slave nodes, and the MB3480 can manage up to 124 
serial slave nodes. Each RS-232/422/485 serial port can be configured 
31 RTU/ASCII slaves per serial port. For RTU/ASCII masters, up to 32 
TCP slaves are supported.
Modbus TCP slaves can be made accessible to serial masters. The 
MB3180, MB3280, and MB3480 offer features that make network 
integration easy, customizable, and compatible with almost any 
Modbus network.
individually for Modbus RTU or Modbus ASCII operation and for 
different baudrates, allowing both types of networks to be integrated 
with Modbus TCP through one Modbus gateway.
 
Convert between Modbus TCP and Modbus RTU/ASCII
 
1 Ethernet port and 1, 2, or 4 RS-232/422/485 ports
 
16 simultaneous TCP masters with up to 32 simultaneous 
requests per master
 
Easy hardware setup and configuration
Ethernet Interface
Number of Ports: 1
Speed: 10/100 Mbps, Auto MDI/MDIX
Connector: 8-pin RJ45
Magnetic Isolation Protection: 1.5 KV built-in
Serial Interface
Number of Ports: 
MB3180: 1 
MB3280: 2 
MB3480: 4
Serial Standards: RS-232/422/485, software selectable
Connectors: DB9 male
ESD Protection: 15 KV for all signals
RS-485 Data Direction Control: ADDC® (automatic data direction 
control)
Serial Communication Parameters
Data Bits: 7, 8
Stop Bits: 1, 2
Parity: None, Even, Odd, Space, Mark
Flow Control: RTS/CTS, DTR/DSR (RS-232 only)
Baudrate: 50 bps to 921.6 Kbps
Serial Signals
RS-232: TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
RS-422: Tx+, Tx-, Rx+, Rx-, GND
RS-485-4w: Tx+, Tx-, Rx+, Rx-, GND
RS-485-2w: Data+, Data-, GND
Software
Operation Modes: RTU Slave, RTU Master, ASCII Slave, ASCII Master
Utilities: MGate Manager for Windows 98/ME/NT/2000, Windows 
XP/2003/Vista/2008/7 x86/x64
Multi-master and Multi-drop: 
Master mode: 32 TCP slaves 
Slave mode: 16 TCP masters (request queue 32-deep for each master)
Bonus Feature: Smart Routing
Physical Characteristics
Housing: Metal, IP30 protection
Weight: 
MGate MB3180: 340 g 
MGate MB3280: 360 g 