Overview 
 
INSYS GPRS 5.0 Ethernet 
 
12
 
 
 
 
 
 
 
 
 
 
 
 
Dez-06
 
3.4.3  Power Supply 
The INSYS GPRS Ethernet requires a power supply of 10 to 60 V (DC) at a maximum of 5% 
ripple. 
 
 
Caution - No overvoltage protection! 
The INSYS GPRS Ethernet does not have a fuse.  
Surges and excessive voltages may result in the destruction of the de-
vice. 
 
The following table shows the values that were determined for a signal field strength of 
26 and an ambient temperature of 
77°F (25°C). The current consumption and therefore 
the power consumption may increase during poor network conditions. The threshold 
value tolerances are subject to the typical fluctuations. A maximum of one value may be 
operated in the threshold value range. 
These are average values for estimating the current consumption. The current consump-
tion during data transmissions may also increase if the antenna is not adjusted correctly. 
This can occur for the following cases: 
  The antenna and/or the antenna cable are not adjusted to 50 Ω impedance. 
  The antenna that is being used is misaligned due to the situation at the instal-
lation site (metal parts, …). 
 
 
State:  
Standby
 
State:  
CSD Data transmission
 
State:  
GPRS Data transmission
 
Current consumption type at 
10 V (DC)
 
140 mA
 
195 mA
 
290 mA
 
Current consumption type at 
24 V (DC)
 
60 mA
 
84 mA
 
121 mA
 
Current consumption type at 
36 V (DC)
 
42 mA
 
60 mA
 
60 mA
 
Power consumption approx.
 
1.4 W
 
2 W
 
2.9 W