General Warning
 
Warning!  After checking controls by manual readjust-
ment, make sure they are always returned to their 
proper settings. 
NEVER attempt to operate a boiler that has failed to 
pass all the safety checks outlined below.   
 
 
 
 
 
 
4.4.1  Test of Ignition Safety System 
 
 
high limit
reset
high limit/operating 
temperature
adjustments
lo-hi-lo 
controller
"on"/"off" 
switch
fuel
selector 
switch
flame control
reset switch
propane
in-use
indicator
 
 
Figure 4-5  Lo-Hi-Lo Control Panel (faceplate opened) 
 
high limit
reset
high limit temperature 
adjustment
"on"/"off" 
switch
flame control
reset switch
operating temperature
adjustment
propane in-use
indicator and 
fuel selector switch
(on side)
 
 
Figure 4-5a  On-Off Control Panel (faceplate opened) 
 
 
The boiler is provided with an ignition safety system. 
1.  Open the faceplate on the control panel.  Discon-
nect wire # 17 (Lo-Hi-Lo) or # 26 (On-Off) at the 
terminal block on the control panel.  Disconnect-
ing this wire disables the main gas valve, ensuring 
that gas cannot flow during the test. 
2.   Turn on the circulating water pump.  With the 
natural gas shutoff and secondary shutoff open 
and the pilot gas cock open, turn the operating 
temperature control until the boiler cycles “on. 
3.  Observe the operation of the boiler.  After all the 
safety limits on gas pressure, water flow, and tem-
perature are satisfied, the blower will run and pre-
purge the boiler.  When air flow is established, the 
ignition transformer and pilot will operate.  Both 
functions will be indicated by separate green 
lights on the control panel.  If a satisfactory pilot 
is established, the green "Ignite" light will extin-
guish and the pilot will remain on, alone, for 10 
seconds.  After 10 seconds, the green "Main Gas" 
light will go on.  (The main gas valve will not 
open with the wire disconnected and gas cannot 
flow to the burner).  The "Pilot" will remain on, 
along with the "Main Gas," for another 10 seconds 
and then go out.  Since the main flame cannot be 
burning, at this point there will be no flame signal 
and the flame safeguard programmer will assume 
a "Flame Failure" and will either re-cycle through 
the complete pre-purge and ignition cycle or, if in-
 
 
- 8 -