Справочник Пользователя для Siemens Welding System ST PCS 7
Process I/O
ET 200M distributed I/O
DI - digital input modules
11/15
Siemens ST PCS 7 · November 2007
11
B) Subject to export regulations: AL: N, ECCN: EAR99H
SM 321 for non-floating contacts (supply with AC voltage)
8 inputs, 120/230 V AC
• Electrically isolated in groups
• Electrically isolated in groups
of 1
• Front connector required:
40-contact
6ES7 321-1FF10-0AA0
B)
SM 321 modules with diagnostics capability
(IM 153-2 High Feature interface module required)
(IM 153-2 High Feature interface module required)
for floating contacts (supply with DC voltage)
16 inputs, 24 V DC
Redundant design possible
(module and channel redun-
dancy)
• Electrically isolated in groups
Redundant design possible
(module and channel redun-
dancy)
• Electrically isolated in groups
of 16
• Time stamping in association
with IM 153-2 High Feature, ac-
curacy 5 ms, rising or falling
edge, can be parameterized
channel-granular
curacy 5 ms, rising or falling
edge, can be parameterized
channel-granular
• Two short-circuit-proof sensor
supplies for 8 channels each
• Sensor supply by the module,
additional external redundant
sensor supply possible
• Diagnostics of missing sensor
supply for channel group
(8 channels)
• Diagnostics inside module
• Wire break monitoring
• Front connector required:
• Wire break monitoring
• Front connector required:
20-contact
6ES7 321-7BH01-0AB0
■
Selection and Ordering Data
Order No.
16 inputs, NAMUR
Redundant design possible
(module redundancy)
• Electrically isolated in groups
Redundant design possible
(module redundancy)
• Electrically isolated in groups
of 8
• Time stamping in association
with IM 153-2 High Feature, ac-
curacy 5 ms, rising or falling
edge, can be parameterized
channel-granular
curacy 5 ms, rising or falling
edge, can be parameterized
channel-granular
• Two sensor supplies (8.2 V DC
or 18 V DC each)
• Connection of NAMUR sensors
or contacts with resistor circuit
• Pulse stretching
• Channel-granular diagnostics
• Channel-granular diagnostics
(short-circuit, open-circuit, chat-
ter monitoring, discrepancy with
changeover contacts)
• Diagnostics inside module
• Front connector required:
• Front connector required:
40-contact
6ES7 321-7TH00-0AB0
■
Selection and Ordering Data
Order No.
© Siemens AG 2007