  MACH®  Series
 
Gas-Fired Boiler 
Installation 
 
 
Page  24 
Analog Input to Adjust Setpoint: 
 
Analog Input S etpoint
0
50
100
150
200
0
1
2
3
4
5
6
7
8
9
10
V oltage
Bo
il
e
r S
e
tp
o
in
t
B oiler Setpoint
Non adjustable C urve
 
 
The control must be configured for a remote analog 
input setpoint according to the following table: 
 
Item Parameter 
Value 
°F 
Allowable 
Range °F 
Maximum Setpoint 
180 
68-185 
Minimum Setpoint 
80 
60-140 
Boiler Configuration 
34 
03 
 
 
 
The setpoint of the boiler is controlled by an external 
0-10 VDC signal. A signal of at least 0.5 VDC is 
required to start the boiler. At 0 VDC the setpoint is 
32° F; at 10 VDC the setpoint is 212° F.  This setpoint 
is low and high limited by maximum and minimum 
setpoint parameters.  The controlled setpoint voltage 
range narrows when these limits are used.  If the above 
tables values are used the boiler setpoint will be 80° F 
when the voltage is anything less than approximately 3 
VDC.  It will then increase linearly with voltage until 
approximately 8.5 VDC when it will be 180° F.  The 
setpoint will remain at 180° F even if voltage is 
increased further.  
 
 
Analog Input to Control Firing Rate: 
 
Analog Input Firing Rate
0
10
20
30
40
50
60
70
80
90
100
0
1
2
3
4
5
6
7
8
9
1 0
V oltag e
Fi
ri
n
g
 R
a
te
 
 
The control must be configured for analog input 
direct drive by setting parameter 34 to 02. 
The firing rate of the boiler is controlled by an 
external 0 to 10 VDC signal.  At a voltage greater 
than 0.5 VDC the boiler turns on and runs at low fire 
until 1.8 VDC is reached. The firing rate increases 
linearly with voltage until high fire is reached at 10 
VDC.  The boiler setpoint Parameter 4 remains active 
to shut down the boiler when the temperature in the 
boiler exceeds this value plus the high temp 
differential.  These voltage levels, as explained 
above, are all “non-adjustable”. 
 
3.12.2  Gas Pressure Adjustment 
 
Note:  Adjustments shall only be performed by 
service representative specifically trained and 
certified to perform maintenance on the 
Patterson-Kelley MACH Series boiler. 
 
See rating plate for the minimum and maximum gas 
pressure of the boiler.  Each boiler is furnished with a 
manual shut-off valve which has an integrated test 
port.