Installation
  
(for qualified installers only)
 
25 
© Travis Industries 
4090507 
100-01217_000 
Side Vent Configuration with Vertical Termination 
•  The termination must fall 
within the shaded area 
shown in the chart.  Use 
the indicated restrictor 
and diffuser positions. 
•  Up to four elbows (45° 
or 90°) may be used. 
•  Only one horizontal 
elbow may be used. 
5 feet (1.5m)
0 feet
0 feet
5 feet (1.5m) 
0 feet
20 feet (6m)
20 feet (6m)
5 feet (1.5m)
10 feet (3m)
5 feet (1.5m)
10 feet (3m)
0 feet
15 feet (4.5m)
20' max (6m)
10 feet (3m)
15 feet (4.5m)
15 feet (4.5m)
20' max (6m)
10 feet (3m)
15 feet (4.5m)
40' max (12m)
Exhaust Restrictor # 4
Intake Restrictor # 2
Diffuser Position # 1
25 feet (7.5m)
30 feet (9m)
35 feet (10.5m)
40' max (12m)
25 feet (7.5m)
30 feet (9m)
35 feet (10.5m)
Exhaust Restrictor # 2
Intake Restrictor # 1
Diffuser Position # 1
This is considered a horizontal 
elbow (it does not matter 
whether it turns right or left).
It may be a 90° or 45° elbow.
This is considered a 
vertical elbow
Horizontal length is calculated by adding 
both lengths of horizontal run 
(Horizontal Length = H1 + H2).
H1
H2