Installation
  
(for qualified installers only)
 
© Travis Industries 
4090507 
100-01217_000 
Packing List 
• 
Propane Conversion Kit 
• Log 
Set 
• 
Firestop (sku 93006094) 
• 
Right Side Standoffs (2) 
• 
Wall Switch, Cover Plate, and Wire 
• 
4 AA Batteries, 1 9-Volt Battery 
• 
Insulation for Side Vent Conversion 
Additional Items Required  
• Direct 
Vent 
• 
Gas Line Equipment (shutoff valve, pipe, etc.) 
• 
Electrical Equipment (min. 14 gauge, grounded line)
 
• 
Two Grill Kits and/or Faces
 
Recommended Installation Procedure 
• 
Prepare the framing, making sure to leave the area around the fireplace open (see page 12).  Make sure to allow for vent 
installation and facing depth. 
• 
Place the fireplace into position. 
• 
Install the vent, gas line and electrical hook-up. 
• 
Finalize the framing around the fireplace. 
• 
Secure the fireplace to the framing. 
• 
Install the wall switch (see page 17) or thermostat (if applicable). 
• 
Install the drywall. 
• 
Install the hearth (if applicable). 
• 
Install the facing (if applicable). 
• 
Install the mantel (if applicable). 
• 
Finalize the installation (see page 38) and install the grill or face. 
Side Standoff Installation 
The two right-side standoffs included with this 
fireplace are attached to the fireplace prior to 
placing the fireplace into position.  These standoffs 
are not required for safety purposes.  Their purpose 
is to center the fireplace in the framed opening. 
Attach the right side standoffs to the fireplace as 
shown below.  Remove the five screws on the side 
of the fireplace, position the standoff, and secure. 
NOTE:  The side standoffs have obround holes that 
allow for the standoff to be adjusted for 
drywall of ½” or 5/8” thickness.  See 
“Nailing Brackets” on page 13. 
 
 
Framing Notes 
The framing dimensions included in this installation manual have been revised to include the extra 1-1/2” 
needed for the right standoffs to install correctly (44” width).  If the fireplace opening has been framed to the 
dimensions listed in the previous version of the installation manual (42-1/2” width), the right side standoffs 
may be excluded.  In this type of installation, the center of the glass will not be located in the center of the 
framed opening.  The center of the glass will be ¾” from the center of the framing.