Справочник Пользователя для Enterasys Networks SecureStack C2RPS-CHAS2
Installing C2RPS-CHAS2 into the Rack
2-4 Installation
To install a PSM, proceed as follows:
1.
Align the PSM with the slot, then slide the PSM forward until its front panel is flush
against the chassis front panel.
against the chassis front panel.
2.
Fasten the PSM to the chassis using the captive screws.
3.
Perform steps 1 and 2 for each PSM being replaced. When completed, proceed to
“
“
Installing C2RPS-CHAS2 into the Rack
To install the chassis into a 19‐inch (48.3‐cm) rack, you need four user‐supplied screws to
fasten the chassis to the rack rails.
fasten the chassis to the rack rails.
After installing the PSM(s) as described back in “
rack mount the chassis as follows:
1.
Refer to the installation guidelines (“
2.
Install the chassis into the rack (“
3.
Connect the PSM cables and AC power cords (“
Guidelines for Rackmount Installation
The installation site must be within reach of the network cabling and meet the
requirements listed below:
requirements listed below:
•
Chassis placement close enough to connect the 2‐meter (6.6‐foot) AC power cords
from the PSMs to the AC power source.
from the PSMs to the AC power source.
•
Up to two three‐pronged power receptacles capable of delivering the current and
voltage specified in “
voltage specified in “
” on page A‐2. Up to two AC outlets
on independently‐fused circuits must be within 182 centimeters (6 feet) from the
installation site. If there is an AC power source failure, this will prevent the powering
down of PSMs due to a single source power failure.
installation site. If there is an AC power source failure, this will prevent the powering
down of PSMs due to a single source power failure.
•
Power cords and type of outlet are dependent on the country. In the United States,
one power cord with an NEMA 5‐15P plug is provided with each C2RPS‐PSM.
one power cord with an NEMA 5‐15P plug is provided with each C2RPS‐PSM.
•
An ambient temperature of between 5°C (41°F) and 40°C (104°F) must be maintained
at the installation site with fluctuations of less than 10°C (18°F) per hour.
at the installation site with fluctuations of less than 10°C (18°F) per hour.
Note: If you plan to remove and not replace a C2RPS-PSM, immediately reinstall
coverplates over any empty power supply slots to prevent EMI leakage from the chassis.
coverplates over any empty power supply slots to prevent EMI leakage from the chassis.