Hardware Connections
 
 
 
 
Warning: The AC Power should 
be wired just as labeled on the  
three pin connector
.  
 
 
    
PIN 1-Ground 
    PIN 2-Line 110v. 
    PIN 3-Line Neutral
                 
 
 
 
 
Grounding Considerations
 
 
     
The grounding is a most important consideration in an installation where 
microprocessor technology is applied.  The EMO-500 is a panel mounted unit and 
therefore the casing is connected to the sub-panel.  If the sub-panel is metal it should be 
grounded.  If the sub-panel is non-conductive - PIN 1 of the three pin connector on the 
EMO-500 back panel must be grounded
 
 
To insure a proper ground we recommend connecting PIN 1 of the three pin 
connector to the panel's central ground point.
 
 
Signal and Shielding 
 
     The two flow meter pick-ups should be supplied with their respective 18v. supply 
voltages and referenced to their respective grounds. This will insure that the input signals 
from the flow meters are referenced to the ground connections on pins 2 and 5.  Most 
applications require some signal shielding.  A solid aluminum wrap shielding will work 
fine.  The shield should be connected to pins 2 and 5 on the flow meter connector.  DO 
NOT connect the shielding at the flow transmitter. 
 
 
 
 
IMPORTANT! NEVER CONNECT THE SHIELD TO GROUND AT BOTH ENDS!! 
DOING SO CAN PRODUCE UNWANTED OSCILLATIONS IN THE SIGNAL WIRES.