 Geo Brick Drive User Manual 
Pinouts and Software Setup 
 52 
 
 
Note 
These  MACRO  IC0  Clock  settings  are  optimized  for  a  good  Analog 
Output  signal.  If  the  Brick  is  a  MACRO  Ring  Controller  then  the 
analog output signal quality is compromised with a much lower PWM 
frequency, or should not be used at all. 
 
For Help with clock calculations, download the Delta Tau Calculator: 
  
 
J9 Analog Output Suggested M-Variable 
// I/O 10 & 11 Mode (PWM) 
M7051->Y:$78404,10,1 
M7052->Y:$78404,11,1 
M7051=0  
; =0 PWM, =1 PFM 
M7052=0  
; =0 PWM, =1 PFM 
 
// Analog Output M-variable  
M7050->Y:$78412,8,16,S 
 
// These I/O nodes have to be setup once on power-up.  
// power-up PLC Example 
Open PLC 1 clear 
I6612=100*8388608/I10 While(I6612>0) Endw 
M7051=0 ; PWM mode 
M7052=0 ; PWM mode  
Disable PLC 1 
Close 
 
Testing the J9 Analog Output 
With I6800=816, writing directly to the assigned M-variable (i.e. M7050) should produce the following: 
 
M7050 
Single-Ended: 
Gnd  Output+ 
Differential: 
Output+  Output- 
 
-10V 
-20V 
-408 
-5V 
-10V 
0V 
0V 
408 
+5V 
+10V 
816 
+10V 
+20V 
 
 
 
Note 
Writing values greater than I6800 (i.e. 816) in M7050 will saturate the 
output  to  10,  or  20  volts  in  single-ended  or  differential  mode 
respectively   
 
 
Note 
MACRO connectivity provides more solutions for analog outputs, e.g. 
using ACC-24M2A.