WHL-016 REV. 3.4.15 
 
Figure 13 
– Multiple Boilers – Primary/Secondary Piping – Circulators - NOTES: 
1. This drawing is meant to show system piping concept only. Installer is responsible for all equipment and detailing required by local codes. 
2. All closely spaced tees shall be within 4 pipe diameters center to center spacing. 
3. A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream of all closely spaced tees. 
4. The minimum 
pipe size for connecting a indirect water heater is 1” 
5. The minimum pipe size for connecting an 055/080/110 - 1
”, 155/199/285 – 1.25”, 399 – 1.5”. 
6. Circulators are shown with isolation flanges. The alternative is standard flanges with full port ball valves. Purge valves can be used with circulator 
flanges as an alternative. 
7. A mixing valve is recommended if the DHW temperature is set above the factory setting of 119
o
F. 
8. Piping shown is Primary/Secondary. System flow (secondary loop) must be greater than the boiler’s primary loop flow. 
9. Install a minimum of 12 diameters of straight pipe upstream of all circulators. 
10. VERY IMPORTANT 
– Minimum flow rates outlined in this manual must be maintained through the heat exchanger to minimize short cycling.