1 Outline
1.3 Cautions on Creation of Fundamental Programs
21
FXCPU Structured Programming Manual
[Basic & Applied Instruction]
1
O
utlin
e
2
Instruc
tion Li
st
3
Configurati
on of 
Instruction
4
Ho
w t
o R
ea
Explanati
on of 
Ins
truction
s
5
B
asic
 Instruction
6
Step Ladder 
Instruct
ions
7
Ap
pl
ied Inst
ruct
io
ns 
(Program Flow)
8
Appl
ied
 In
stru
cti
ons 
(Mov
e and 
C
omp
are)
9
App
lie
d Instr
uction
(Ari
thm
eti
c and
 
Lo
gic
al O
per
at
ion)
10
App
lied Inst
ructi
ons 
(Rot
ati
on and 
Shift O
perati
on)
1.3.2
Double output (double coil) operation and countermeasures
This subsection explains the double output (double coil) operation and countermeasures.
1. Operation of double output
When a coil (output variable) is used twice (double coil) in another program block to be executed or in the
same program block, the PLC gives priority to the last coil.
Suppose that the same coil Y003 is used in two positions as
shown in the figure on the right.
For example, suppose that X001 is ON and X002 is OFF.
In the first coil Y003, the image memory turns ON and the output
Y004 turns ON also because the input X001 is ON.
In the second coil Y003, however, the image memory is set to
OFF because the input X002 is OFF.
Accordingly, the actual output to the outside is "Y003 = OFF,
Y004 = ON".
2. Countermeasures against double output
Double output (double coil) does not cause an illegal input (program error), but the operation is disrupted as
described above. Change the program as shown in the example below.
SET, RST or jump instruction can be used instead, or a same output coil can be programmed at each state by
using step ladder instructions STL or RET.
When you use the step ladder instruction STL or RET, note that the PLC regards it as double coils if you
program, inside the state, an output coil located outside the RET from another program block or the STL
instruction.
X001
  Input processing
  X001=ON   X002=OFF
First
Y003
X002
Second
  Output processing
  Y003=OFF   Y004=ON
Y003
Y004
Y003
A
B
Ignored
C
E
D
A
B
C
E
D
A
B
C
E
D
M100
M101
Or
Y000
Y000
Y000
M100
M101
Y000