30 Applied Instructions (External Device Communication)
30.7 ADPRW / MODBUS Read/Write
725
FXCPU Structured Programming Manual
[Basic & Applied Instruction]
21
Appl
ied
 In
stru
cti
ons 
(R
eal
 T
im
C
lock
 Contr
ol)
22
Ap
plied
 Instru
ctio
ns 
(E
xt
er
na
l De
vi
ce
)
23
App
lied Instr
ucti
ons 
(Ex
tensi
on 
Functi
on)
24
Ap
pl
ied In
struct
ions 
(O
thers)
25
Appl
ied
 Instru
cti
ons
 
(B
lock
 Dat
O
per
at
io
n)
26
App
lie
d Instr
uction
(Charac
ter 
Stri
ng C
ontrol
)
27
Ap
pl
ied Inst
ruct
io
ns 
(D
ata
 Op
eration 3
)
28
Appl
ied
 In
stru
cti
ons 
(D
ata C
om
par
ison
)
29
App
lie
d Instr
uction
(D
ata
 T
abl
O
peration
)
30
Appli
ed In
struc
tions
(E
xt
ernal Devi
ce 
Comm
uni
cat
ion)
Cautions
1) The instruction is provided in the FX
3U
 and FX
3UC
 PLCs Ver. 2.40 or later.
The instruction is provided in the FX
3G
 PLC Ver. 1.30 or later.
2) It is not permitted to use an "ADPRW" instruction and a following instruction for the same port:
- "RS or RS2" instruction
- "IVCK, IVDR, IVRD, IVWR, IVBWR
*1
, IVMC" instruction
- "FLCRT
*1
, FLDEL
*1
, FLWR
*1
, FLRD
*1
, FLCMD
*1 
or FLSTRD
*1
" instruction
3) Some restrictions to applicable devices
S1: Excluding special auxiliary relays (M) and Special data register (D).
S2: The FX
3U
 and FX
3UC
 PLCs only are applicable.
*1.
The instruction is not provided in the FX
3S
, FX
3G
 and FX
3GC
 PLCs.
30.7.1 Command Code and Parameters
The following table shows the required command parameters for each command code.
1H
Read Coils
MODBUS Address:
0000H to FFFFH
Device Count: 1 to 2000
PLC Destination Device (head address)
Applicable Devices D, R, M, Y, S
Block Length
(
+15) 
÷16
*2
2H
Read Discrete
Inputs
MODBUS Address:
0000H to FFFFH
Device Count: 1 to 2000
PLC Destination Device (head address)
Applicable Devices D, R, M, Y, S
Block Length
(
+15) 
÷16
*2
3H
Read Holding
Register
MODBUS Address:
0000H to FFFFH
Device Count: 1 to 125
PLC Destination Device (head address)
Applicable Devices D, R
Block Length
4H
Read Input 
Register
MODBUS Address:
0000H to FFFFH
Device Count: 1 to 125
PLC Destination Device (head address)
Applicable Devices D, R
Block Length
5H
Write Single Coil
MODBUS Address:
0000H to FFFFH
0 (fixed)
PLC Sourse Device (head address)
Applicable Devices
D, R, K, H, X, Y, M, S
(D, R, X, Y, M, S can be
indexed.)
Block Length
1 Point
6H
Write Single
Register
MODBUS Address:
0000H to FFFFH
0 (fixed)
PLC Source Device (head address)
Applicable Devices
D, R, K, H
(D, R can be indexed.)
Block Length
1 Point
7H
Read Exception
State (Available only in
FX
3U
 and FX
3UC
 PLCs)
0 (fixed)
0 (fixed)
PLC Destination Device (head address)
Applicable Devices D, R
Block Length
1 Point
8H
Diagnosis
(Available only in FX
3U
and FX
3UC
 PLCs)
Sub-function: 0H
Loop-back Test
Sub-function Data
(loop-back data): 0 to 65535
Loop-back Test Data
(Slave response: echo of 
)
Applicable Devices D, R
Block Length
1 Point
Sub-function: 1H
Restart
Communication
Sub-function Data:
0x0000: Do Not Reset
Event Log
0xFF00: Reset Event Log
(Slave response: echo of 
)
Applicable Devices D, R
Block Length
1 Point
Sub-function: 2H
Return
Diagnostic Register
0 (fixed)
PLC Destination Device (head address)
Applicable Devices D, R
Block Length
1 Point
*2.
This calculation formula is applicable when the applicable device is D or R.