5) SOOTING 
Make sure log placement is 
in the correct location. 
Correct to manufactures 
specifications. 
Correct if necessary. 
Outside air supply may be 
required on B-vented 
models. 
Make sure there is sufficient 
air supply. 
Check air shutter on the 
venturi tube for proper 
primary air adjustment. 
SEE PAGE 16. 
Increase primary air. 
 
Open air shutter. 
Make sure orifice matches 
that on the rating plate. 
Correct if necessary. 
Make sure outlet (manifold) 
pressure is correct. 
Use a manometer to check 
the gas pressure. 
SEE PAGE 5 FIGURE 7. 
Make sure the unit has been 
derated for high altitude 
applications. 
(if required) 
Correct if necessary. 
Check to make sure that the 
vent is drafting properly. 
Correct if necessary. 