4.2.48 OL signal output timer (Pr. 157)
Pr. 157 "OL signal waiting time"
Use this parameter to set whether the overload alarm signal (OL signal) is output immediately or a preset
period of time after occurrence of an overload status.
<Setting>
Refer to the following table and set the parameter:
Parameter 
Number
Factory Setting
Setting Range
Remarks
157
0
0 to 25 s, 9999
9999: No signal output
Pr. 157 Setting
Description
0
Output immediately.
0.1 to 25
Output after the set time (s) has elapsed.
9999
Overload alarm signal is not output.
R elated param eters
Pr. 190 to Pr. 195
 "output terminal function selection"
Set time (s)
Overload status (OL output)
L output signal
Pr. 158     Refer to Pr. 54.