Справочник Пользователя для Mitsubishi Electronics FR-A500

Скачать
Страница из 257
185
4
4.2.64 Droop control (Pr. 286, Pr. 287)
Pr. 286 "droop gain"
Pr. 287 "droop filter constant"
This function balances the load in proportion to the load torque with or without encoder, and provides speed
drooping characteristics.
This is effective in balancing the load when using multiple inverters.
z
 The output frequency is varied according to the amount of torque current during unbalanced flux vector
control and vector control.
The drooping amount at the rated torque is set by the droop gain as a percentage using the rated
frequency as a reference.
z
 Confirm the following items when using the droop control.
1. This function is valid when Pr. 286 
 "0" during unbalanced flux vector and vector control.
2. This function is valid when the operation state is constant speed operation.
3. The upper limit of the droop compensation frequency is 120Hz.
4. The rated current follows the value set in Pr. 9 "motor rated current".
<Setting>
Refer to the following table and set each parameter.
Parameter No.
Factory setting
Setting range
286
0%
0 to 100%
287
0.3s
0.00 to 1.00s
Parameter No.
Details
286
Set the drooping amount at the rated torque as a percentage with respect to the rated 
frequency.
When the setting value is "0", the function will be invalid.
287
Set the time constant of the filter applied on the torque amount current.
Related parameters
Pr. 9 "electronic thermal O/L relay"
Pr. 71 "applied motor"
Pr. 84 "rated motor frequency"
Droop compensation frequency =
Amount of torque current after filtering
Rated current
Rated frequency droop gain
100
Droop compensation
frequency
Torque
100
%
Droop gain
-100
%
Frequency
0
Rated frequency
Pr. 342     Refer to Pr. 117.